Input: 220-240 Vac 50Hz
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
Note 1: Optional manual
wall switch for overriding off.
L
230 VAC
N
N
L
SL
DIAGRAM C (WIRING A SINGLE PIR)
INPUT:
Voltage:
220 - 240Vac
Frequency:
50Hz
LOADING:
Resistive loads:
6 amps (1500W)
Fluorescent:
6 amps (1500W)
LED Drivers and LED
6 amps (1500W)
lamps and fittings:
Electronic and wire
3 amps (750W)
wound transformers:
CFL and 2D lamps:
2 amps (500W)
Fans:
1 amp (250W)
2W resistive, suitable
for most energy
Minimum load
saving lamps, LEDs
and emergency
fittings.
OPERATING CONDITIONS:
The temperature difference between the
detection target and the background must
be at least 4 °C.
Ambient
-20... +40 °C (lout
temperature:
0.05 A)
PRECAUTIONS AND WARRANTY
This product conforms to BS EN 60669-2-1 and
BS EN 55015.
Please ensure the most recent edition of the
appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp
circuit breaker and voltage surge protection.
Please ensure that this device is disconnected
from the supply if an insulation test is made.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
13/04/2021
WIRING DIAGRAMS
Note 2:
Alternative
position for
optional
load
wall switch
CESF PIR
TECHNICAL DETAILS
Max. case
temperature:
Storage
temperature:
Max. relative
humidity:
CONNECTORS:
Terminal block
Wire size:
Wire strip length:
Tightening torque:
MECHANICAL DATA:
Dimensions:
Weight:
Degree of
protection:
Protection class:
Material (casing)
Finish / Colour
Protection class:
Other DANLERS Product ranges
- Remotely adjusted PIR occupancy switches
- Manually adjusted PIR occupancy switches
- Daylight linked dimming controls
- Photocell switches
- Time lag switches
- Outdoor security switches
- Dimmer switches inc. LED dimming
- HVAC controls
- Radio remote (RF) controls
Note 1: Optional manual
wall switch for overriding off.
L
230 VAC
N
N
L
SL
CESF PIR
DIAGRAM D (WIRING IN PIRS IN PARALLEL)
CONFORMITY AND STANDARDS:
+70 °C
EMC emission:
-25... +75 °C
EMC immunity:
0... 80%, non cond.
Safety:
0.5mm
2
- 2.5mm
2
Environment:
solid or stranded
6-7mm
VARIANTS - LOW VOLTAGE:
0,4 Nm/4 Kgf.cm
DANLERS also design and manufacture an
extensive range of Ceiling Surface Mounted
PIR Occupancy Switch variants some of
86mm x 86mm x
which are listed below:
22mm
CESF PIR 12VAC
98g (unpacked)
CESF PIR 12VDC
CESF PIR 24VAC
CESF PIR 24VDC
IP20
CESF PIR 12VACVF
Built-in Class 2
CESF PIR 12VDCVF
CESF PIR 24VACVF
Flame-retardant
CESF PIR 24VDCVF
polycarbonate
Matt /White (RAL
9003)
Built-in Class 2
Please call for more information or visit
our website.
This product is covered by a warranty which
extends to 5 years from the date of manufacture.
(Presence detection)
Note 2:
Alternative
position for
optional
load
wall switch
N
L
SL
CESF PIR
EN60669-2-1:2004
inc. A12:2010
EN60669-2-1:2004
inc. A12:2010
EN60669-2-1:2004
inc. A12:2010
Complies with
WEEE and RoHS
directives
12V or 24V (ac or
dc) operation
12V or 24V (ac or
dc) operation Volt
Free contacts
DAT0098 CESFPIR