Low voltage variants can be supplied, coded by the following suffixes:
• 12VAC
12V - (ac supply) operation
• 12VDC
12V - (dc supply) operation
• 24VAC
24V - (ac supply) operation
• 24VDC
24V - (dc supply) operation
Trouble shooting
The COPD cannot be made to switch on during bright days
• The COPD should have the lux set to inactive via the internal mode
button (see diagram B)
The PIR does not detect
• Person is too far from the COPD switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
The PIR stops working
• Ensure the unit is mounted correctly so that no water can enter.
The PIR False triggers
• Detector is exposed to air movement on breezy days.
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
01/03/19
Compact person detector, PIR switch
COPD
DANLERS Compact Person Detector is IP66 rated and can be
surface mounted onto an external wall. It incorporates a passive
infra-red quad sensor to detect movement of a warm body within
the detection zone (diagram A) and the COPD (BK) includes a
photocell to monitor the ambient light level.
The detection range is about 10 metres over 120 degrees, the range
reduces to about 8m at the extremes to prevent nuisance switching.
On detecting movement, if the ambient light is dark enough, the
COPD (BK) will switch the load on. The ambient threshold can be
set by the user to between approximately 10 and 1000 lux via the
internal LUX adjuster (diagrams B and C). The photocell can be
disabled via the internal mode button (see overleaf).
If no more movement is detected within a pre-selected time,
then the PIR switch will turn the load off. This time lag can be set
via the TIME adjuster to 10 seconds, 20 seconds, 40 seconds,
80 seconds, 2 minutes 30 seconds, 5 minutes,10 minutes, 20
minutes or 40 minutes (diagram D).
Product codes:
COPD
COPD BK
Loading
The switch should only be connected to a 230V 50Hz AC supply.
These PIR switches can switch up to:
6 amps (1500W) of resistive loads.
6 amps (1500W) of fluorescent loads.
3 amps (750W) of electronic and wire wound transformer loads.
2 amps (500W) of CFL, 2D lamps, LED Drivers and LED lamps
and fittings.
1 amp (250W) of fans
Minimum load 2W resistive, suitable for most energy saving lamps,
LEDs and emergency fittings.
INS970 COPD
Installation notes
COPD BK
Grey enclosure
Black enclosure