TECHNICAL SPECIFICATIONS
DESCRIPTION
Input Voltage Range
Current Requirements
No relays Operating
One Relay Enabled
All Relays Enabled
Heat Dissipation
One Relay Enabled
All Relays Enabled
Relay Contacts
Current Rating
Resistance
Operating Temperature
Physical Dimensions
Weight
46032-05-0199 <90-00146>
OPERATION
T
he relays operate on presence of +5 VDC. There is no
latching capability. The relay contacts open when that
voltage is removed. The individual LED should light on the front
panel as power is applied to each relay. This, however, does not
verify correct relay contact operation — only that voltage is
applied to that individual relay.
-21 to -56 VDC
@ -21VDC
@ -24 VDC
0.0 mA
0.0 mA
7.4 mA
8.4 mA
118.0 mA
134.0 mA
@ -21VDC
@ -24 VDC
0.5 Btu/Hr
0.7 Btu/Hr
8.5 Btu/Hr
11.0 Btu/Hr
1 Amp @ 30 VDC
0.1 Ohm
0° to 55° C.
1.4" x 6.0" x 5.6"
7.5 Ounces
DESCRIPTION
@ -48 VDC
@ -56 VDC
0.0 mA
0.0 mA
10.4 mA
11.6 mA
172.8 mA
185.6 mA
@ -48 VDC
@ -56 VDC
1.8 Btu/Hr
2.2 Btu/Hr
28.3 Btu/Hr
35.5 Btu/Hr