To set the desired humidity level press
Press
and set the operating threshold (SHC) at humidity change. To apply the settings and
to leave the menu press
For example. The operating threshold (SHC) is set at 2%. If PV parameter value is 2% above
SV parameter value the device will stop automatically till PV parameter value is 2% lower
than SV parameter value. As soon as this condition is fulfilled the device will switch on again.
The humidifier default setting is 80%. The desired humidity can be set from 0% to 100%.
Attention! It is not allowed to place the remote humidity sensor in the area directly
Maintenance
To assure the humidifier long-time and trouble-free operation its timely cleaning and
maintenance is required.
Prior to any operations on the humidifier it is necessary to disconnect it from the
electric network and to drain water from the tank using a cock located on the
Before a long shut-down period it is necessary to drain water from the tank, remove the
tank top panel, wipe with a dry cloth and let the device to dry out.
After a long period of operation various hard deposits can form on the tank surface and
on the piezoelectric radiators panel which have a negative effect on spraying. To assure
nominal humidification it is necessary to keep the panel with radiators free of any deposits. It
is prohibited to use household detergents for tank and radiator panel cleaning. Do not touch
the nozzles. Cleaning should be carried out at least 1 time per month. Proceed as follows :
·
open the top panel;
·
wipe the tank and the upper part of the piezoelectric radiators panel with a soft cloth or
brush;
·
wash the tank and the panel with flowing water. Avoid water contact with electronic
components. It can cause a short circuit;
·
wipe the surfaces with a dry cloth and replace the top panel.
If the humidifier is used with interruptions it is required to change the water in the tank on a
regular basis.
Water filter cleaning should be carried out at least once a month. For this purpose proceed as
follows:
·
open the water filter housing;
·
wash the filter element;
·
assemble the filter.
Attention! The supplied water quality strongly influences the device durability. To
improve the water quality it is recommended to use additional filters for dematerialized
The air filter located behind the front removable panel is to be maintained as well. The
filter condition should be checked at least once a month. If the filter condition is unsatisfactory
it must be replaced.
The piezoelectric radiators panel is subject to replacement after 5000 operating hours.
For the nozzle panel replacement contact an authorized service center.
After the radiators panel or the float valve replacement it is necessary to check the
panel depth relative to the tank water surface and if necessary adjust the depth. The depth is
adjusted with a screw located on the float valve.
www.danvex.fi
R
, then use
again.
exposed to water mist!
humidifier housing.
water treatment.