Contemporary Control Systems BASRTP-B Посібник з монтажу - Сторінка 16

Переглянути онлайн або завантажити pdf Посібник з монтажу для Бездротовий маршрутизатор Contemporary Control Systems BASRTP-B. Contemporary Control Systems BASRTP-B 20 сторінок.

those passed by the router from BACnet/IP. The default value
usually provides good performance.
MS/TP Baud Rate
(Default Value = 9600)
The baud rate of the MS/TP network can be 9600, 19200, 38400
or 76800 bps. All MS/TP devices on the same MS/TP network
must use the same baud rate. On power up the router checks for
other masters; if finding none, it begins token passing — at which
point autobauding devices will adjust to the router's baud rate.
MS/TP Tolerance
(Default Selection = Strict)
This setting determines the degree to which interoperability with
devices is successful. The Lenient option is less efficient for
traffic flow but optimizes interoperability. A slight improvement
in performance will be realised by selecting the Strict setting.

Status Screen

The Status Screen depicted in Figure 11 reports the traffic of the
various protocols handled by the BASRTP-B.
It shows the
number of messages received and transmitted for each of the
supported networks.
Note: ―BIP 1‖ is the only BACnet/IP port in use. Although it
appears in the screen, ―BIP 2‖ is not used in this version of the
product. Therefore, the counts of ―BIP 2 Incoming Packets‖ and
―BIP 2 Outgoing packets‖ will always be 0.
―Available Memory‖ (at the bottom of the list) is the amount of
RAM currently unused (normally about 30K). If one network is
temporarily offline and another network is attempting to
communicate with this network, the available memory may drop
very low until the offline network returns to an online condition.
The remaining information indicates the instantaneous MS/TP
state of the router and is documented in the MS/TP portion of the
BACnet standard.
―RFSM‖ is the current Receive Frame State Machine state.
―MNSM‖ is the current Master Node State Machine state.
TD070210-0ID