Contemporary Controls CTRLink EIBA5-100T/R Посібник з монтажу - Сторінка 3

Переглянути онлайн або завантажити pdf Посібник з монтажу для Перемикач Contemporary Controls CTRLink EIBA5-100T/R. Contemporary Controls CTRLink EIBA5-100T/R 4 сторінки. Building automation 10/100 mbps switching hubs

Contemporary Controls CTRLink EIBA5-100T/R Посібник з монтажу
Power Options
Power Considerations
Voltage in the range of 10–36 VDC or 24 VAC ± 10%
must deliver current commensurate with power
consumption. Size conductors accordingly. Ground is
directly connected to zero volts and the chassis is
isolated from zero volts. Input connections are
reverse-polarity protected.
LED Indicators
To aid troubleshooting, each port LED glows solid if a
link exists, flashes to show activity and shows data rate
by colour: green for 100 Mbps and yellow or 10 Mbps.
One power LED is provided.
Network Connections
The switch employs Auto-MDIX technology so that
either straight-through or crossover cables can be used
to connect to NIMs or another hub.
Mechanical — EIBA5-100T/R