Data Aire LonWorks dap4 Інструкція з експлуатації - Сторінка 7

Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Мережева карта Data Aire LonWorks dap4. Data Aire LonWorks dap4 10 сторінок.

Description
Cooling Utilization Over Last
Hour -Percentage of cooling is
used in the last hour of
operation; this point applies to
DX unit.
Heating Utilization Over Last
Hour -Percentage of heating is
used in the last hour of
operation
Humidifier Utilization Over Last
Hour -Percentage of humidifier
is used in the last hour of
operation
Compressor 1 Runtime -This
point applies to DX unit with one
compressor -high
Compressor 1 Runtime -This
point applies to DX unit with one
compressor -low
Compressor 2 Runtime -This
point applies to DX unit with
dual compressor - high
Compressor 2 Runtime -This
point applies to DX unit with
dual compressor - low
Heater 1 Runtime - high
Heater 1 Runtime - low
Humidity upper limit alarm
Upper limit alarm of return air
temp
Humidity setpoint
CW valve open % (0-100% with
10% increment)
Chilled Water Utilization Over
Last Hour - This applies to
Chilled water or Energy saver
units.
Humidifier Runtime - high
Humidifier Runtime - low
Blower Runtime - high
Blower Runtime - low
Document number 600-000-966 Ver. 3
Dap4 LonWorks Interface Instructions
Read/
Variable Name
Write
R
Comp_duty
R
Heat_duty
R
Hum_duty
R
C1_Hours_H
R
C1_Hours_L
R
C2_Hours_H
R
C2_Hours_L
R
Ht1_Hours_H
R
Ht1_Hours_L
Write
Hum_Hi_SP
only
Write
Ret_Air_Hi_SP
only
R/W
Hum_setpoint
R
CW_disp
R
WtrVlv_duty
R
Hum_Hours_H
R
Hum_Hours_L
R
Blower_Hours_H
R
Blower_Hours_L
Data
LONworks
Type
I
nvoCoolUtlz
I
nvoHeatUtlz
I
nvoHumUtlz
I
nvoC1_Hours_H
I
nvoC1_Hours_L
I
nvoC2_Hours_H
I
nvoC2_Hours_L
I
nvoHt1_Hours_H
I
nvoHt1_Hours_L
I
nviHiHumLimit
I
nviHiTempLimit
I
nvoHumSetpoint /
nviHumSetpoint
I
nvoValve
I
nvoChillUtlz
I
nvoHum_Hours_H 8
I
nvoHum_Hours_L 8
I
nvoFan_Hours_H
I
nvoFan_Hours_L
SNVT
8
8
8
8
8
8
8
8
8
8
105
8
8
8
8
8
7