iNode Care Sensor PHT – instruction manual
The picture below shows the Barometer tab:
The following items can be set:
Alert if pressure is:
no alarm: the device does not respond to pressure changes.
greater than: device sends an alert in case a set threshold pressure value is exceeded.
less than: device sends an alert in case a set threshold pressure value is exceeded.
out of range: sends an alert in case a crossing one of the set pressure threshold.
in range: device sends an alert, in case that the pressure is between set pressure values.
You can change the pressure threshold value or values in the range from 261 hPa to 1269 hPa.
Archive alerts: the device saves the time of the beginning and end of any of the events selected
above.
Archive pressure: the device keeps the record measured pressure every 1 minute.
Pressure correction: the user can adjust the measured pressure in the range from -100 hPa to
+100 hPa with a resolution of 0,1 hPa.
You can save modified settings by pressing the Write button.