Elsema MD2010 Посібник - Сторінка 5

Переглянути онлайн або завантажити pdf Посібник для Датчики безпеки Elsema MD2010. Elsema MD2010 6 сторінок. Loop detector

Feature
Pulse mode
Presence mode
The MD2010 must be reset every time a setting change is made to the Dip-switches
Reset
*Please note: The MD2010 must be reset every time a setting change is made to the Dip-switches
Relay status:
Relay
Presence mode
Pulse mode
Power up or Reset (Loop testing)
On power up the detector will automatically test the sensing loop.
Ensure the sensing loop area has been cleared of all loose pieces of metal, tools and vehicles before powering up
or resetting the detector!
Dip Switch settings
Pulse mode or Presence mode (Dip switch 8)
Dip switch 8 "OFF"
Dip switch 8 "ON"
Reset (Dip switch 9)
Dip switch 9
"ON/OFF"
Vehicle Present
N/O
Closed
N/C
Open
N/O
Closes for 1 sec
N/C
Opens for 1 sec
Description
Pulse mode. Relay will activate for 1 sec only on entry
or exit of sensing loop area as set by dip-switch 6. To
re-activate the vehicle must leave the sensing area and
re-enter.
Presence mode. Relay will remain active, as per dip-
switch 5 selection, for as long as a vehicle is within the
loop sensing area.
To reset, switch dip-switch 9 on for approximately 2
seconds and then off again. The detector then
completes the loop test routine.
No vehicle
Loop faulty
present
Open
Closed
Open
Closed
5
ELSEMA
No Power
Closed
Closed
Open
Open
Open
Open
Closed
Closed
MD2010