Dataprobe K-410 Посібник - Сторінка 4

Переглянути онлайн або завантажити pdf Посібник для Подовжувачі Dataprobe K-410. Dataprobe K-410 6 сторінок. Remote control

Series K-x20, K-x15 & K-x10
Page 4
Power Input and Output Connections
CAUTION Be sure to check that the unit is set to the correct operating voltage before plugging in the
unit or applying AC power. Make certain to disconnect the K-81x from the AC power source before
making any control connections.
A/C Power Connections
The K-820 & K-420 provide a linecord for connection to a 20 Amp 115VAC service. The total maximum current
load for all outlets on the K-820 or K-420 cannot exceed 16 Amps.
The K-815 & K-415 provide a linecord for connection to a 15 Amp 115VAC service. The total maximum current
load for all outlets on the K-815 or K-415 cannot exceed 12 Amps.
The K-810 & K-410 are for international applications and can be set for use on 115V or 230VAC. The K-810 &
K-410 provide an IEC 320 style universal inlet for connecting a detachable power cord. A standard IEC to
NEMA 5-15 cord set is supplied with the unit for use on 15 Amp 115VAC service. The total maximum current
load for all outlets cannot exceed 12 Amps at 115VAC or 10 Amps when used at 230VAC.
The K-810 & 410 are selectable for 115VAC or 230 VAC operation. The voltage selector switch is
located on the left side of the unit near the input connector ( Viewed from rear panel). Make sure the
switch is in the proper position before applying power.
The K-810 uses IEC320 connectors for the switched output. Dataprobe offers IEC to IEC jumper
cables to assist in connection to PC, Router, etc that has IEC Connection
Order Cable
921-14-0016 IEC to IEC 3' long
921-14-0018 IEC to IEC 6' long