3.3.7 Long press SET button for 6 seconds, the display will start flashing E1 code, when E1
keeps flashing you press SET button again the code will switch from E1, E2, E3, E4, E5, F1,
F2, F3 and F4. When staying in a specific code you can press UP or DOWN button to
change the parameter according to your need. Every codes represents something you can
calibrate by yourself, and here below is what it means by each code:
Code
Setting
To calibrate the
E1
temperature
lower range
To calibrate the
E2
temperature
upper range
Compressor OFF
E3
Temperature
Compressor
KICKS IN
E4
temperature
Compressor
E5
retardation time
Temperature
F1
Display Calibrate
(for 0 ~ -6°C)
Temperature
F2
Display Calibrate
(for -6 ~ -12°C)
Temperature
display Calibrate
F3
(for below -12°C)
Celsius to
F4
Fahrenheit
(Note: F4 is after F3 code, but it will not display F4 wording, instead the digit number keeps
flashing).
3.3.8 How to resume to factory default setting: In E1 code (see 3.3.7), press UP and DOWN
button at the same time for 6 seconds, the digit number will read 888, 6 seconds later it will
resume to the factory default setting.
Default
Range
Value
-20°C
-40°C
10°C
40°C
1°C
1~10°C
1°C
1~10°C
1~10
3 minutes
minutes
-5 ~ 5°C
-5 ~ 5°C
-5 ~ 5°C
°C
4
Details
The default lowest temperature you can set is -20°C,
maximum you can set it to be -40°C, which means after
you reset this value, you can select your desire
temperature lower than -20°C (lowest -40°C), the
compressor will not stop running until the interior
temperature goes to -40°C.
Same principle as E1
In default value 1°C, assuming you set the temperature to
be 5°C, when the temperature gets to 4°C (1°C lower
than 5°C), the compressor will shut off automatically; if
you change the value to be 2°C, the compressor will shut
off when temperature gets to 3°C (2°C lower than 5°C)
In default value 1°C, assuming you set the temperature to
be 5°C, when the interior temperature rise up to 6°C (1°C
higher than 5°C), the compressor will resume to run; if
you change the value to be 2°C, the compressor will
resume to work when the interior temperature rise up to
7°C (2°C higher than 5°C).
In default value, if you plug the refrigerator to the electric
power source, the compressor will wait 3 minutes before
running. You can change the time from 1 to 10 minutes
according to your need.
If you find the displaying temperature does not match the
real temperature, you can calibrate the temperature
display within the range. For example if the real
temperature is 2°C but it displays 0°C, you can change
the parameter to be 2°C, then the display will read 2°C
instead of 0°C.
Same as F1. Between -6 ~ -12°C, for example, the real
temperature is -6°C but it displays -8°C, you can change
the parameter to be 2°C, then the display will read -6°C
instead of -8°C.
Same as F1. For temperature below -12°C, for example if
the real temperature is -14°C but it displays -16°C, you
can change the parameter to be 2°C, then the display will
read -14°C instead of -16°C.
Switch between °C and °F.