Datexel DAT 1111 Інструкція з монтажу

Переглянути онлайн або завантажити pdf Інструкція з монтажу для Передавач Datexel DAT 1111. Datexel DAT 1111 2 сторінки. Low profile, dip-switch programmable and linearised transmitter

Via monte Nero, 40/B – 21049 TRADATE (VA) ITALY
Phone: +39 (0)331841070 Fax:+39 (0)331841950 -
FEATURES
- Input from Pt100
- Input scale in °C or °F
- Zero and Span programmable by DIP-switches
- 4÷20 mA current loop linearised output
- Good accuracy and linearity
- EMC compliant – CE mark
- Suitable for DIN B in-head mounting
- Option for DIN rail mounting in compliance with EN 50022 (DIN RAIL Option)
GENERAL DESCRIPTION
The transmitter DAT 1111 is designed to provide on output a 4÷20 mA current loop linearised signal proportional with the temperature characteristic provided
from the Pt100 connected to its input.
It is possible to connect on input both Pt100 3 wires and Pt100 2 wires sensors.
It is possible to program the input range by the 4 way DIP-switches available removing the protection plastic cap located on the top of device (see the section
"Input ranges table").
The regulation of the zero and full-scale value are made using the ZERO and SPAN potentiometers.
The DAT 1111 is in compliance with the Directive 2004/108/EC on the Electromagnetic Compatibility.
It is housed in a self-extinguish plastic enclosure suitable for DIN B in-head mounting.
Moreover ( by proper mounting kit ) it is possible to mount the DAT 1111 on DIN rail.
USER INSTRUCTIONS
The transmitter DAT 1111 must be powered by a direct voltage between 10 to 32 V applied to the terminals +V and -V.
The 4÷20 mA output signal is measurable in the power loop as shown in the section "Output/Power supply connections"; Rload is the input impedance of
instruments on the current loop; to obtain a correct measure, the value of Rload will be calculated as function of the power supply value ( see section " Load
characteristic").
The input connections must be made as shown in the section "Input connections".
The Pt100 three wires must be connected to the terminals 1 and 3, connecting the third wire to the terminal 2.
The Pt100 two wires must be connected to the terminals 1 and 3, connecting the terminal 2 and 3.
The configuration of the input range must be made by DIP-switches. To configure the device refer to the section "Input ranges table".
Regulate the output value by the ZERO and SPAN regulations.
To calibrate and install the transmitter refer to sections " DAT1111: configuration and calibration" and "Installation Instructions".
Input
Sensor type
Minimum input Span
Zero programmability
Span programmability
Excitation current
Line resistance influence
Output
Output type
Sensor interruption signalling
Maximum output signal
Load resistance (Rload)
Response time (from 10 to 90 % of f.s.)
Warm-up time
Performances
Calibration error
Linearity error (*)
Thermal drift
Power supply voltage (**)
Electromagnetic Compatibility (EMC)
( for industrial environments )
Operating Temperature
Storage Temperature
Humidity (not condensed)
Weight
(*)inclusive of hysteresis, linearisation error and power supply voltage variation
(**)internally protected against reverse polarity.
TECHNICAL SPECIFICATIONS (Typical at 25 °C and in nominal conditions)
-
www.datexel.it
RTD Pt100 in according to IEC 60751
50 °C (122 °F)
From -50 °C (-58 °F) up to + 50 °C (122 °F)
From 50 °C (122 °F) up to 650 °C (1202 °F)
1 mA typ.
0.05 % of f.s./ohm (100 ohm max. balanced per wire)
4 ÷ 20 mA on current loop
Positive out of scale (> 20 mA)
35 mA
see section "Load characteristic"
300 ms
3 min.
± 0.1 % of f.s.
± 0.15 % of f.s.
0.03 % of f.s./°C
10÷32 Vdc
Immunity: EN 61000-6-2; Emission : EN 61000-6-4.
-20 ÷ 70 °C
-40 ÷ 85 °C
0 ÷ 90%
about 35 g.
Low profile, dip-switch
programmable and linearised
transmitter for Pt100
DAT 1111
DAT 1111