Technische Daten
Isolationskoordination nach IEC 60664-1
Definitionen:
Versorgungskreis ........................................................................BB-Bus
Ausgangskreise ............................Relaiskontakte (13, 14)...(123, 124)
Sichere Trennung (verstärkte Isolierung) zwischen ...............................
.................................................................(BB-Bus) – (Relaiskontakten)
Bemessungsspannung .......................................................... 250 V
Überspannungskategorie ............................................................ III
Verschmutzungsgrad ................................................................... 2
Bemessungs-Stoßspannung .................................................... 6 kV
Spannungs-/Stückprüfung nach IEC61010-1................. AC 3,51 kV
Basisisolierung zwischen ...................(Relaiskontakt) – (Relaiskontakt)
Bemessungsspannung .......................................................... 250 V
Überspannungskategorie ............................................................ III
Verschmutzungsgrad ................................................................... 2
Bemessungs-Stoßspannung .................................................... 4 kV
Spannungs-/Stückprüfung nach IEC61010-1................. AC 2,21 kV
Versorgungsspannung
Versorgungsspannung U
.......................................................... DC 24 V
s
Toleranz von U
................................................................................5 %
s
Eigenverbrauch .........................................................................< 1,7 W
LEDs
ON (Betriebs-LED) ...........................................................................grün
Schaltglieder
Anzahl ................................................................................12 Schließer
Bemessungsbetriebsspannung .................................. AC 250 V/DC 30 V
Bemessungsbetriebsstrom ................................................................5 A
Minimale Kontaktbelastbarkeit ................................1 mA bei ≥ DC 5 V
Umwelt/EMV
EMV .......................................................................IEC 61326-2-4
Umgebungstemperaturen:
Arbeitstemperatur .........................................................-25°C...+55°C
Transport .......................................................................-40°C...+85°C
Lagerung........................................................................-25°C...+70°C
Klimaklassen nach IEC 60721:
Ortsfester Einsatz (IEC 60721-3-3) ................................................. 3K22
Transport (IEC 60721-3-2) ............................................................. 2K11
Langzeitlagerung Einsatz (IEC 60721-3-1) ..................................... 1K22
Mechanische Beanspruchung nach IEC 60721:
Ortsfester Einsatz (IEC 60721-3-3) .................................................. 3M4
Transport (IEC 60721-3-2) .............................................................. 2M4
Langzeitlagerung Einsatz (IEC 60721-3-1) .................................... 1M12
Einsatzhöhe ............................................................ ≤ 2 000 m über NN
Technical data
Insulation coordination according to IEC 60664-1
Definitions:
Supply circuit .............................................................................. BB bus
Output circuits .............................. relay contacts (13, 14)...(123, 124)
Protective separation (reinforced insulation) between ..........................
.................................................................... (BB bus) – (Relay contacts)
Rated voltage ........................................................................ 250 V
Overvoltage category ................................................................. III
Pollution degree .......................................................................... 2
Rated impulse voltage ........................................................... 6 kV
Voltage/routine test acc. to IEC61010-1 ........................ AC 3.51 kV
Basic insulation between .....................(relay contact) – (relay contact)
Rated voltage ........................................................................ 250 V
Overvoltage category ................................................................. III
Pollution degree .......................................................................... 2
Rated impulse voltage ............................................................ 4 kV
Voltage/routine test acc. to IEC61010-1 ........................ AC 2.21 kV
Supply voltage
Supply voltage U
...................................................................... DC 24 V
s
Tolerance of U
.................................................................................5 %
s
Power consumption ..................................................................< 1.7 W
LEDs
ON (operation LED) .......................................................................green
Switching elements
Number ......................................................................... 12 N/O contacts
Rated operational voltage ......................................... AC 250 V/DC 30 V
Rated operational current .................................................................5 A
Minimum contact rating .............................................1 mA at ≥ DC 5 V
Environment/EMC
EMC ..................................................................................IEC 61326-2-4
Environment temperatures:
Operating temperature .................................................-25°C...+55°C
Transport .......................................................................-40°C...+85°C
Storage ..........................................................................-25°C...+70°C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ...................................................... 3K22
Transport (IEC 60721-3-2) ............................................................. 2K11
Long-term storage (IEC 60721-3-1) .............................................. 1K22
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ..................................................... 3M11
Transport (IEC 60721-3-2) .............................................................. 2M4
Long-term storage (IEC 60721-3-1) .............................................. 1M12
Range of use .............................................................. ≤ 2,000 m AMSL
IOM441-S_D00300_04_M_DEEN / 03.2022