4.
Corrective Actions
As corrective action the O-ring needs to be replaced and a spacer plate needs to
be added to each HI-FOG 1900 sprinkler installed in A1000 type assembly body
with an internal stop valve.
Note: These instructions are intended for HI-FOG systems with electric
powered pump units.
For GPU (Gas-driven Pump Units) please contact Marioff for system
specific instructions.
4.1. Required Documents and Tools
To assure all affected sprinklers are addressed, it is recommended to prepare a
work plan before starting the work.
The following documents are recommended to be used in the process:
• HI-FOG sprinkler layout drawing to provide the locations of all potentially
affected sprinklers, section valves and flushing valves which will be used
during the modification process.
Please note that even though the HI-FOG sprinkler layout drawings indicate
HI-FOG 1000 sprinklers they may have been replaced by HI-FOG 1900
sprinklers during testing or service.
• Appendix A of this document contains a follow-up table for the checking and
adjusting of sprinklers.
Required parts:
• Spacer Ring, Marioff item code 2000267114
• O-Ring 15x2,0, Marioff item code 2000297566
Spacer plate
Required tools (see
• O-Ring assembly tool; item code 2000297565
• Sprinkler key; item code M11015 or Sprinkler dismounting tool; item code W-
0010888
• Flushing hose; item code M14510 or Section valve test hose; item code
D23050 or Section valve test hose; item code D23040
• Buckets and rags as some spillage is expected when removing and
reinstalling the sprinklers
Document number 0003301084
Figure 04 : Required parts
Figure 05
for details):
Ver. A
O-Ring 15x2,0
Page 5 of 18