 Configuration directives
th1=**, set the motion detection sensitivity. Integer setting. The default configuration is th1=120. The higher
the value, the less sensitive the module is. The sensing distance and range are smaller. The FOV under the reference
sensitivity setting is given later.
th2=**,set the presence detection sensitivity. Integer setting. The default configuration is th2=250. The higher the value,
the less sensitive the module is to presence detection. The sensing distance and range are smaller. The FOV at the reference
sensitivity setting is given later. Generally, the sensitivity can not be adjusted.
dtime=**, set the GPIO delay detection time. Integer setting. The default configuration is dtime=5. A value of 5
is 5S.
mov_sn=**, set the GPIO to pull up the GPIO when it detects several large-scale data. The default
configuration is mov_sn=3, the larger the setting, the less sensitive it is, and it can be increased when there are large
false positives.
occ_sn=**, set how many times small amplitude data is detected after GPIO is pulled high to maintain GPIO
high level. The default configuration is occ_sn=5, the larger the setting, the less sensitive it is. It is not recommended
to increase it.
save, save the parameter settings. If save is not sent, the power-down will fail.
get_all, the module outputs the current parameter settings.
All commands sent with carriage return and line feed are valid.
 Radar output
When the radar detects a larger motion, it outputs mov, ******. (The second number represents the signal strength)
When the radar detects the static state of the human body or small amplitude movements, it will output occ, ******. (The
second number represents the signal strength)
When the radar cannot detect the target, it stops outputting. The user can make a certain delay in the upper layer to
avoid frequent unmanned state when the signal is weak. (The first number represents the spectral line position, the
user can ignore it directly)
Note: The startup time of the module is about 15 seconds, and it starts to output data after 15 seconds of
power-on. Because the module makes existence judgment by accumulating signal characteristics for a period
of time, when the person disappears from the radar detection range, the radar will continue to accumulate
signals for a period of time, so the radar will stop outputting after a period of lag time.
7
Motion status output
The first number represents the
spectral line position,the second
number represents the signal
strength
Static state output