TROUBLESHOOTING GUIDE (PAGE 1 OF 2)
STATUS
INDICATOR (LED)
DISPLAY
DETAIL
LED GREEN
ON Steady,
not flashing
LED flashing
GREEN/
ORANGE
LED flashing
GREEN/OFF
LED steady
OFF, not
flashing
LED RED
steady ON
Emergi-Lite®
Tel: (888) 552-6467
®
SYMPTOMS
Lamp load is on
None if unit is in normally on mode Unit is operating correctly
Lamp load is off
None if unit is in normally off mode Unit is operating correctly
Lamp load is OFF, but
the unit is in normally
The fuses are burnt
on mode
-Lamp load is OFF
(if installation is
Power at primary AC input +
normally OFF)
battery discharged (at LVD) + no
- Lamp load is ON
reaction with test button
(if installation is
normally ON)
None if unit is in normally on mode
Lamp load is ON
+Nexus option
None if unit is in normally off mode
Lamp load is OFF
+Nexus option
None the unit is in test mode or is
Lamp load is ON
sampling load
Inverter switched OFF
Lamp load is OFF
The output fuse is burnt
No power at primary AC input + in
Lamp load is ON
emergency mode
No power at primary AC input +
Lamp load is OFF
emergency mode stop (battery
discharged)
- Lamp load is OFF
(if installation is
Power at primary AC input +
normally OFF)
battery discharged (at LVD) + no
- Lamp load is ON
reaction with test button
(if installation is
normally ON)
Battery Disconnect
No battery installed in the unit
Error
TROUBLESHOOTING GUIDE
PROBLEM
Replace the fuses after verifying that there is no
short circuit in the load
- Remove the primary AC input + disconnect the
battery + wait minimum 10 seconds
- connect the battery + connect the primary AC input
=> the unit will restart
- if the unit did not restart + call the technical support.
Unit is operating correctly. Unit is not commissioned
to the Nexus system
Unit is operating correctly. Unit is not commissioned
to the Nexus system
Unit is operating correctly
Check the inverter ON/OFF switch => Turn it on.
Switch is located on the right side of the inverter
module.
Replace the fuses after verifying that there is no
short circuit in the load
Check the circuit breaker panel
Check the circuit breaker panel
- Remove the primary AC input + disconnect the
battery + wait minimum 10 seconds
- connect the battery + connect the primary AC input
=> the unit will restart
- if the unit did not restart, call for technical support at
1-(888)-552-6467.
Install the battery following the installation guide
Fax: (800) 316-4515
www.emergi-lite.com
EMIU 125/250/400W Mini Inverter
CORRECTIVE ACTION