Automatic Solutions ASA244BS Посібник з монтажу та обслуговування - Сторінка 7
Переглянути онлайн або завантажити pdf Посібник з монтажу та обслуговування для Відкривач воріт Automatic Solutions ASA244BS. Automatic Solutions ASA244BS 14 сторінок. Industrial swing gate operator
Powering Accessories
Accessories which require a 24v AC supply can be powered from the transformer output used to power the
control board and motor. However, the transformer's current capacity must be checked to allow for the
extra power required by the accessories.
Locks & Lights
Use the lock output terminals on the din rail to switch the 12 volts to an electric lock (if fitted). The load
switched by the lock output terminals must not exceed 30v AC / DC @ 5Amps. If a electro magnetic lock
is used, change one wire on the control board lock output to the normally closed output. Use the light relay
module (if fitted) to switch the applied voltage to a light. The load switched by the light relay module must
not exceed 240v AC / 30v DC @ 10 Amps.
Mode Selection
Using the mode selection dip-switches select the desired operating modes. Note the times associated with
the parameters marked with an * can be changed. The auto-close times can be changed using the procedure
in the following section. See the detailed installation manual for details on how to change the other
parameters.
P
1
Synchronising Delay
OSITION
OFF - No delay
ON -
Motor 1 starts to open 2 seconds* before Motor 2 and Motor 2 starts to close 2 seconds* before
Motor 1.
P
2
Pulse Lock Output
OSITION
OFF - Lock output is activated for the entire motor drive cycle.
ON -
Lock output pulses for 0.3 seconds* at the start of each drive cycle.
P
3
Light Outputs Warning
OSITION
OFF - Optional light module controls a light with timer which turns light off after 60seconds*.
ON -
Optional light module controls a warning light which activates whenever motors are on.
P
4
Swipe Mode (OSC Input)
OSITION
OFF - OSC input terminal has standard Open, Close, Stop action.
ON -
OSC input terminal will only open the door/gate. The input also resets the P.E triggered
auto-close mode so that the P.E input will need to be triggered again before a P.E auto-
close cycle will be initiated.
P
5
M 2 Outputs Status
OSITION
OFF - The M2 output controls second motor
ON -
The M2 output controls status lights
P
6
P.E Stops Close Cycle
OSITION
OFF - Activating the P.E input while motors are closing causes the motors to reverse.
ON -
Activating the P.E input while motors are closing causes the motors to stop but not reverse.
P
7
P.E Stops Open Cycle
OSITION
OFF - Activating the P.E input while motors are opening is ignored by the controller.
ON -
Activating the P.E input while motors are opening causes the motors to stop.
P
8
P.E Triggered Auto Close
OSITION
OFF - Not selected
ON -
Selects the P.E triggered auto-close mode which causes the motors to auto-close if the P.E input is
activated then released. (Auto-close delay time is 0 seconds*)
P
9
Pedestrian Auto-Close
OSITION
OFF - No pedestrian access auto-close
ON -
Selects auto-close in the pedestrian access mode. (Auto-close delay time is 15 seconds*)
P
10
Standard Auto Close
OSITION
OFF - Not selected
ON -
Selects standard auto-close mode which will close the motors after fully opening.(Auto-close delay
time is 30 seconds*)
7