DynaGen AST2225 Посібник з встановлення та експлуатації - Сторінка 18

Переглянути онлайн або завантажити pdf Посібник з встановлення та експлуатації для Перемикач DynaGen AST2225. DynaGen AST2225 19 сторінок. Automatic transfer switch

Programming the Exerciser Time Clock
The mode switch slider is in the O or "disable" position when packaged at the factory.
The set switch is in the "run" position.
Use the following steps to program the exerciser time clock for a particular exercise
day, time, and duration:
Move MODE SWITCH to "auto" and the SET SWITCH to "run".
1.
Press the RESET BUTTON using the tip of a pencil or pen. This operation will
2.
produce a blinking display showing "00:0" for the time and an arrow under the day
7 (Sunday).
Move the SET SWITCH slider to the left (clock icon) position so the present day
3.
and time can be set. A default time AM 12:00 appears in the display with an
arrow under the day 7 or Sunday.
Press the DAY button (1..7) repeatedly until the arrow points to the actual day of
4.
the week.
Press the HOUR button (h) repeatedly until the actual time of day is displayed,
5.
such as AM 5:00 or PM 5:00.
Press the MINUTE button (m) repeatedly until the minute of the present hour is
6.
displayed, such as AM 5:30 or PM 5:30.
Move the SET switch slider to the "run" position. The present time is displayed
7.
with the clock colon "
continuously under the present day.
Move the SET switch slider to the "program" position (P in a circle). The default
8.
time for starting an exercise is AM 12:00. The day arrow is absent. A small 1
appears to the right of the time with a lamp symbol above the 1. The 1 (or odd
number) indicates the start of an exercise or contact closure. The lamp symbol
indicates that the exerciser contacts are closed.
Press the DAY button (d) repeatedly until an arrow appears under the desired
9.
exercise day (Monday = 1) for starting the exercise.
Press the HOUR button repeatedly until the desired time for beginning the
10.
exercise is displayed, such as AM 5:00 or PM 5:00.
Press the MINUTE button repeatedly until the minute of the hour for beginning
11.
the exercise is displayed, such as AM 5:30 or PM 5:30.
Manual for AST2225 Series
:
" blinking in one-second intervals. The arrow appears
Automatic
Transfer Switch
18