INSTALLATION
Step 1—Controller Location
The AirCycler® STAT should be installed in a central
location away from any direct airflow from air vents.
The AirCycler® is wired like any conventional thermostat.
Warning: Before installing the AirCycler®, turn off all
power to the furnace. There may be more than one power
to disconnect. Electrical shock can cause injury or death.
1.30 i
Step 2 – Installing the AirCycler®
1.
Remove the AirCycler® cover from wall plate
(mounting base) to expose mounting holes.
2.
Route wires through large hole in the mounting base.
Mount base against wall and mark wall through 3
mounting holes.
3.
Drill 3 - 3/16-in. pilot holes in wall where marked.
4.
Secure mounting base to wall with 3 screws
(provided), making sure all wires extend through hole
in mounting base.
5.
Adjust length and routing of each wire to reach
proper terminal and connector block on mounting
base with 1/4 in. of extra wire. Strip only 1/4 in. of
insulation from each wire to prevent adjacent wires
from shorting together when connected.
6.
Connect wires to proper terminals of the connector
block. (Figure 2) Both (R) and (C) must be connected
for proper operation.
(opt i on al)
Figure 2
7.
Improper wiring or installation may damage the
3.50
controller. Check to make sure wiring is correct
9 cm
before proceeding with installation or turning the
unit on.
8.
Push any excess wire into wall and against mounting
base.
9.
Snap cover onto base making sure pins align with
sockets in connector.
10. Once powered the AirCycler® will automatically
enter into operating mode.
3.4 cm
Figure 3
CONFIGURATION
The three keys on the exterior of the AirCycler are used to
configure the AirCycler®. (Figure 3)
Factory default settings
FAN ON:
10 minutes
FAN OFF:
20 minutes
VENT ON:
10 minutes
VENT OFF:
20 minutes
Heat Pump:
Off
Pump cycling:
Off
Units:
Fahrenheit
Calibrate:
-5
Delta:
2
Press and hold the Increase Key while placing the unit
onto the base to enter the Menu Mode.
Configure FAN ON time
1.
Once in the Menu Mode FAN ON will flash on the
display.
2.
Use the Increase or Decrease Keys to change the
FAN ON time from 1 - 199 minutes or to select
unlimited ON time (UN). UN allows the fan to
operate continuously.
Configure FAN OFF time
1.
Press the Mode Key again to set the FAN OFF time.
FAN OFF will flash on the display.
2.
Use the Increase or Decrease Keys to change the
FAN OFF time or to select unlimited OFF time (UN).
This will turn the AirCycler® off. This will also keep
the AirCycler® off even after power is lost.
4.50 in.
11.5 cm
*The AirCycler® retains settings even after power is lost.
Increase Key
NOTE: In humid climates, the FAN OFF time should be
at least 6 minutes. This allows moisture on the AC coil to
dry, preventing condensation in cold supply ducts.
Mode Key
ON/OFF
Configure VENT ON time
1.
Press the Mode Key. VENT ON will flash.
2.
Use the Increase or Decrease Keys to change the
Decrease Key
VENT ON time.
Configure VENT OFF time
1.
Press the Mode Key. VENT OFF will flash.
2.
Use the Increase or Decrease Keys to change the
VENT OFF time.
Configure Heat pump functions
1. Press the Mode Key. HP will flash.
2. Use the Increase Key or Decrease Key to toggle
between ON and OFF.
Configure Pump cycling
Enables pump cycling for combination domestic hot
water based systems. ON will cycle the pump for 55
seconds if there has been no call for heating in 24 hours.
1. Press the Mode Key. PC will flash.
2. Use the Increase Key and Decrease Key to toggle
between ON and OFF.
Configure Units
The temperature reading can be displayed in Celsius or
Fahrenheit.
1. Press the Mode Key. UN will flash
2. Use the Increase Key and Decrease Key to change
the units to Fahrenheit or Celsius.
Calibrate
The temperature reading can be calibrated to a known
source for the most accurate temperature reading.
1.
Press the Mode Key. -x will flash.
2.
Use the Increase Key and Decrease Key to calibrate
the AirCycler® to a known source.
Configure the Delta for the set-point.
The delta prevents the system from short cycling.
1.
Press the Mode Key. d2 will flash.
2.
Use the Increase Key and Decrease Key to increase
and decrease the Delta.
Save Settings
To complete the set up press the Mode Key again to
save the settings and to enter into Operating Mode.
Otherwise the AirCycler® will back out of Menu Mode
automatically without saving the settings.
3.50 i
9 cm
OPERATING MODE
Once installed and powered, the AirCycler® will
automatically enter into Operating Mode.
The current mode will be displayed alternating with the
current temperature reading.
1.30 i
Modes
3.4 cm
HT = heating mode
CL = cooling mode
OF = off
To change the mode press the Mode Key. Continue to
press the Mode Key until the desire mode is displayed
(heating (HT), cooling (CL) or off (OF)) .
To change the temperature set-point use the Increase
Key and Decrease Key.
If the AirCycler® activates heating, cooling, or constant
fan operation, the display will read FAN ON.
When the fan turns on, the damper will open and the
display will read VENT ON. Once the VENT ON time has
expired, the damper will close, the display will read FAN
ON until the AirCycler® turns the fan off.