I N STALLATI ON GUI DE
Appendix B
See Section 3: Wiring to clarify the procedures in this appendix.
B.1

Network Defaults Jumper Procedures

Use the applicable Network Defaults Jumper procedure to correct potential errors in an EDGE EVO and
EDGE EVO Solo controller Network Configuration or if the admin password is not available.
EDGE EVO (EH400-K)
This Network Defaults Jumper procedure requires physical access to the EDGE EVO controller. Physical
access provides the necessity to place a jumper over the debug port prior to the controller rebooting.
The controller reconfigures the network settings to the factory defaults when the jumper is on the
debug port during a reboot. From this point, configuration (or re-configuration) proceeds normally.
A jumper is supplied with the EDGE EVO for the Hi-O termination; borrow this jumper to perform this
process. Replace the jumper to the Hi-O termination after restoring network defaults.
1.
Remove the back plate on the EDGE EVO.
2.
Loosen the Mylar cover.
Note: For the jumper location, see the diagram in Section 3: Wiring.
3. Reboot the controller and place the supplied jumper over pins 3 and 5 of the Debug port after
the beep. The Debug port is an eight pin header, located above and to the right of the Ethernet
connector, underneath the Mylar.
Note: The network reset opportunity occurs for 30 seconds, while rebooting the controller. On an
EDGE EVO, a second beep occurs to signal the end of the 30 second period.
4. After 30 seconds, the beeper stays on constantly to indicate success. When an error occurs, you
receive a single beep.
5. Remove the jumper; return it to the Hi-O termination header and cycle power. The controller
resets in approximately 60-seconds. Once the reset is complete, you hear the single beep. After
the 30-second window, you hear the second beep. The controller is fully functional during this
time.
CAUTION: During the controller rebooting process, all network configuration information is
overwritten and returned to the original defaults.
6. Configure the controller for your installation parameters.
7.
Reinstall the back plate of the EDGE EVO.

Troubleshooting

Page 9
An ASSA ABLOY Group brand
EDGE EVO
82000-921, Rev. D.3