WARNING:
To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate
the installation and operation of your equipment. These codes vary
from area to area and it is your responsibility to determine which
codes should be followed, and to verify that the equipment, instal-
lation, and operation are in compliance with the latest revision of
these codes.
Equipment damage or serious injury to personnel can result
from the failure to follow all applicable codes and standards. We
do not guarantee the products described in this publication are
suitable for your particular application, nor do we assume any
responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or opera-
tion of this equipment, or if you need additional information, please
call Technical Support at 770-844-4200.
This publication is based on information that was available at
the time it was printed. At AutomationDirect.com® we constantly
strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time
without notice and without any obligation. This publication may also
discuss features that may not be available in certain revisions of
the product.
Removable Terminal Block Specifications
Part Number
P2-RTB
Number of
18 Screw Terminals
Positions
30-16 AWG (0.051 - 1.31 mm²)
Solid / Stranded Conductor
Wire Range
3/64 in. (1.2 mm) Insulation Maximum
1/4 in. (6-7 mm) Strip Length
Conductors
"USE COPPER CONDUCTORS, 75°C" or Equivalent.
Screw Driver
Width
Screw Size
M2
Screw Torque
2.5 lb·in (0.28 N·m)
*Recommend Screw Driver TW-SD-MSL-1
4
www.productivity2000.com
P2-RTB-1
18 Spring Clamp Terminals
28-16 AWG (0.081 - 1.31 mm²)
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum
19/64 in. (7-8 mm) Strip Length
0.1 inch (2.5 mm) Maximum*
N/A
N/A
General Specifications
Operating Temperature
0° to 60°C (32° to 140°F)
Storage Temperature
-20° to 70°C (-4° to 158°F)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
>10MΩ @ 500 VDC
Heat Dissipation
1800mW
Enclosure Type
Open Equipment
UL508 file E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System.
Use ZIPLink Wiring System or removable terminal
Field Wiring
block (not included). See "Wiring Options" on
page 2.
See the "EU Directive" topic in the Productivity
EU Directive
Suite Help File. Information can also be obtained
at: www.productivity2000.com
Connector Type (not included) 18 Position Removable Terminal Block
Weight
97.6g (3.4oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
LED Status
Fault Condition
Fault Status Indication
Missing External 24VDC V1 LED is ON
Open Load (Note 1)
Over Temperature or
F LED is ON (Note 2)
Over Load Current
Note 1: Open Load Fault is always enabled, but is only valid when output is OFF. If Open
Load Fault happens while output is ON, fault will not appear until you turn OFF
output.
Note 2: The SEL button cycles between the output status and fault status. If the "F" LED is
OFF the numbered LEDs are showing output status. If the "F" LED is ON the
numbered LEDs are showing fault status of each output. The "V1" LED is
independent of fault or output display.
Tech Support 770-844-4200
Operation to Reset Fault
Apply external 24 VDC
Connect the load
Turn the output OFF or
cycle power