Automationdirect.com Productivity P1-04DAL-1 Посібник

Переглянути онлайн або завантажити pdf Посібник для Блок управління Automationdirect.com Productivity P1-04DAL-1. Automationdirect.com Productivity P1-04DAL-1 8 сторінок. Analog output

Automationdirect.com Productivity P1-04DAL-1 Посібник

Output Specifications

Output Channels
Output Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Output Type
Output Value in Fault Mode
Load Impedance
Maximum Inductive Load
Allowed Load Type
Maximum Inaccuracy
Full Scale Calibration Error
Offset Calibration Error
Accuracy vs. Temperature
Max Crosstalk at DC, 50Hz and
60Hz
Linearity Error (End to End)
Output Stability and
Repeatability
Output Ripple
Output Settling Time
All Channel Update Rate
Maximum Continuous Overload
Type of Output Protection
Output Signal at Power Up and
Power Down
External Power Supply Required
Sales 800-633-0405
4
4-20 mA
12-bit
4-20 mA = 3.9 µA / count
1 LSB = 1 count
0-4095 counts
Current sourcing at 20mA max
Less than 4mA
0-570 Ω (19.2 VDC), 0-690 Ω (21.6 VDC),
0-810 Ω (24.0 VDC), 0-930 Ω (26.4 VDC),
0-1100 Ω (30.0 VDC)
Minimum Load: 0Ω @ 0-45 °C
125Ω @ 45-60 °C ambient temperature
1mH
Grounded
1% of range
±0.2% of range minimum
±0.2% of range maximum
±75 PPM / °C maximum full-scale
calibration change (±0.005% of range / °C)
-72dB, 1 LSB
±4 counts max., (±0.1% of full scale)
±2% counts after 10 min. warm up (typical)
±0.2% of full scale
0.3 ms max., 5µ min. (full scale range)
2ms (max)
Outputs open circuit protected
Electronically current limited to 20mA or less
4mA
24VDC (-20% / +25%) @ 140mA (Loop
Power Included)
P1-04DAL-1 Analog Output
P1-04DAL-1
The P1-04DAL-1 Low Resolution Analog Output
Module provides four current sourcing channels for
converting a digital value of 0-4095 (12-bit) to 4-20
mA analog signals for use with the Productivity1000
system.
Output Specifications . . . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Terminal Block Specifications . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
I1+
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
I2+
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
I3+
Typical Application Example . . . . . . . . . . . . . . . . . . 7
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
I4+
0V
COM
COM
COM
COM
4-20mA OUT
Terminal Block sold separately, (see wiring options on page 5).
ANALOG
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement. (See www.productivity1000.com for details).
www.productivity1000.com
1000
1