Performance and data
Overview
The IC7-C and IC9-C meters are 230/400 volt 50 Hz, 5 amp
current transformer operated meter designed for measuring
3 phases in a 4 wire star configured system and is
capable of transmitting kWh and kVAH by means of the
volt free outputs which are standard on the basic model.
The model IC9-C is supplied with a fully programmable
RS485-communication output and is capable of
transmitting all of the data the meter monitors.
Technical Parameters
Meter Standard
Accuracy
Reference Voltage
Basic Current
Maximum Current
Frequency
Pulse Constant (LED strobe) 1000 imp/kWh,
Range of Voltage
Operating Temperature
Storage Temperature
Power Consumption
Pulse Output
Red L.E.D.
Display
Output Details
Pulse Duration
Pulse Value
Diagram 9: Typical load curve with
balanced load at 50 Hz.
BS EN 61036
Active 1.0, Reactive 2.0
3 x 230 /400 v
5 Amp
6 Amp
50/60 Hz
1000 imp/ kVAH
200- 250 volt
-30°C – +70°C
-30°C – +80°C
0.01VA @5A; 0.8W,
8VA @230V
IEC 62053-31
Pulse Indication.
20 x 4 character LCM with
background light.
2 – Opto isolated Mosfet
devices: 400 ACV, 100ma
KWh, KVAH
80-100 ms closure
C.T. Value less than 1000/5A
= 1 kWh/imp
C.T. Value 1000/5A or more
than = 10 kWh/imp
9
IC
Load Curve
0.4
0.3
0.2
0.1
-0.1
-0.2
-0.3
-0.4
0.1
1.0
Current transformer selection
For accurate monitoring, correct selection
of the current transformers is critical.
Always select the current transformers suitable
for the load you are actually monitoring.
DO NOT automatically select current
transformers to the breaker size
in case the load is significantly lower.
Main Function
Measurement and Information available from
Keypad.
1. Active, Reactive, Apparent import energy
2. Active, Reactive export energy
Real Variables
1. Voltage: 3 phase voltages, 3 line voltages
2. Current: 3 phase current and neutral
current
3. Active instant (kW): 3 phase and total
power
4. Reactive instant (KVAR): 3 phase and total
power
5. Apparent (KVA): 3 phase and total power
6. Power factor: 3 phase and total power
factor
7. Frequency
Demand (Demand period 30 minutes)
1. Current Demand: Active, Reactive,
Apparent demand
2. Maximum demand: Active, Reactive,
Apparent Maximum demand
Performance characteristics
2.0
3.0
8
0.5 Lag 1.0
Unity 0.5
Lead
4.0
5.0
6.0