Detach the Case
Front
Plug
• Push the grooves at both side of the product to the outside of the product with a flat
head (-) driver and push the plug to the front to separate it from the case. DIP switch is
located inside.
᜸ Caution: Turn OFF the power before detaching the cover.
᜸ Caution: When using the tools, be careful not to be wounded.
DIP Switch Setting
3 2 1 6 5 4 3 2 1
ON
OFF
SW2
SW1
■ DIP SW1
SW1
Function
1
COUNT IN, RESET input logic
Count up / count down
2
-
3
4, 5
Max. counting speed
Memory retention
6
• Input logic
SW1-1
Input logic
NPN (no-voltage input)
ON
PNP (voltage input)
OFF
• Max. counting speed
SW1
Max. counting speed
5
4
1 cps
OFF
ON
30 cps
OFF
OFF
2 kcps
ON
OFF
5 kcps
ON
ON
■ DIP SW2
SW2
Function
Output operation mode
1, 2, 3
01)
01)  Except the indicator model.
• Output operation mode
SW2
Output operation mode
3
2
1
OFF OFF OFF F
OFF OFF ON
N
OFF C
OFF ON
R
OFF ON
ON
ON
OFF OFF K
P
ON
OFF ON
OFF Q
ON
ON
S
ON
ON
ON
• Detach the case and proceed the
settings. See the 'Detach the Case.'
• How to change the settings:
power OFF → change settings → power
ON → press [RESET] key or input the
RESET signal (≥ 20 ms) to the external
terminal.
Defaults
ON
OFF
OFF
OFF
OFF
• Count up / count down
SW1-2
Count up / count down
Count down
ON
Count up
OFF
• Memory retention
SW1-6
Memory retention
×
ON
OFF
Defaults
OFF
Input Connections
• Input: COUNT IN, RESET
• Max. counting speed in the contact input: 1 or 30 cps setting.
■ No-voltage (NPN) input
• Solid-state input
Sensor
(NPN output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
• Contact input
Counter / Timer
+12 V
5.4 kΩ
Internal circuit
of input part
0 V
■ Voltage (PNP) input
• Solid-state input
Sensor
(PNP output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V
• Contact input
Counter / Timer
+12 V
Internal circuit
of input part
10.8 kΩ
0 V
Input / Output Connections
Brown 12 VDCᜡ
Black
COUNT IN
Sensor
Blue
GND
The capacity of sensor power supply is 12 VDCᜡ 50 mA. Be careful not to exceed the capacity
when connecting the sensor.
Be careful not to let the load capacity exceed the contact capacity.
Sensor
(NPN open collector output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
Sensor
(PNP open collector output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V
4
5
3
6
2
7
Load
1
8
SOURCE