DynaQuip WaterCop Classic Посібник користувача та інструкція з монтажу - Сторінка 11
Переглянути онлайн або завантажити pdf Посібник користувача та інструкція з монтажу для Вимірювальні прилади DynaQuip WaterCop Classic. DynaQuip WaterCop Classic 20 сторінок.
WARNING:
valve must NOT be installed where it could ignite flammable vapors or
explosive mixtures.
To reduce risk of electrical shock, fire, or damage to property or WaterCop®:
Do not use extension cords. Use of extension cords can cause fires or electric
shock. Install WaterCop® within 20 feet of an outlet or, install an outlet near the
WaterCop®. Comply with all local codes.
Before opening case, unplug power cord. When case is open, it is possible to
contact electrified components. Always unplug the power cord before opening the
unit. Wear eye protection for plumbing and electrical work.
NOTICE:
WaterCop® should be installed downstream of existing shut-off valves
and pressure reducers. Install 18" downstream from existing indoor water meters to
allow for future meter maintenance.
Manually Testing the Valve and Wireless Sensors
Manually Test the Valve
To test your WaterCop® Classic System, gently pull the safety plugs out from each end
of the valve . Check the position of the valve by looking in either threaded end .
In the open position, you will be able to see through the valve; in the closed position
only the shiny surface of the ball will be visible . Place the base of the housing
on a sturdy surface, as close as feasibly possible to the location where it will be
permanently installed . Plug the WaterCop® power cord into a nearby 120 VAC outlet .
The valve position indicator lights should now correspond to the actual position you
noticed: Green = Open, Red = Closed . Grasp both sides of the housing (not the valve)
with the valve pointing away from you for safety . Being very careful not to have your
fingers or other objects near the valve openings, press the colored circle just below
the unlit indicator light . You will hear the motor change the valve position . Again,
look into the threaded end of the valve to verify that the valve has changed position .
If it appears that the valve has not turned from one position to the other, DO NOT
try to reposition the valve yourself by inserting any tool or fingers into the valve.
Operate the valve several more times from open to close, checking each time for
proper positioning . If you are experiencing trouble getting the valve to open and shut,
call 800-545-3636 .
Manually Test the Leak Sensors
Leak and Temperature sensors require power to operate . Use either fresh AA alkaline
batteries (not included) and/or a WaterCop® AC Adapter (sold separately) to power .
If both are used, batteries will provide back-up power in the event AC power is lost .
Rechargeable batteries are not recommended . To install batteries, remove the battery
cover located on the back of the sensor and install batteries in accordance with the
(+ and -) placement guide . Reinstall the back plate .
The WaterCop® case is NOT EXPLOSION PROOF. The shut-off
11