Specifications
Model
LE3S
Function
MULTI time, MULTI operation
Display method
LCD (Character size: W 4 × H 8 mm)
Return time
≤ 200 ms
Time operation
Signal ON Start
Input signal
START, INHIBIT, RESET
Min. signal width
≈ 20 ms
Short-circuit impedance
: ≤ 1 kΩ
Short-circuit residual voltage
No-voltage input
: ≤ 0.5 VDCᜡ
Open-circuit impedance
: ≥ 100 kΩ
Control output
Relay
Contact type
Time limit SPDT (1c)
250 VACᜠ 5 A, 30 VDCᜡ 5 A
Contact capacity
resistive load
Repeat
- Power ON Start
SET
: ≤ ± 0.01% ± 0.05 sec
Error
- Signal ON Start
Voltage
: ≤ ± 0.005% ±0.03 sec
Temp.
Approval
ᜢ ᜧ ᜫ
Weight
≈ 100 g
Model
LE3S
Power supply
24 - 240 VACᜠ ± 10% 50 / 60 Hz, 24 - 240 VDCᜡ ± 10%
Power consumption
AC: ≤ 2.5 VA, DC: ≤ 1 W
Insulation resistive
100 MΩ (500 VDCᜡ megger)
Dielectric strength
2000 VACᜠ 50 / 60 Hz for 1 min
Noise immunity
± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲)
0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each
Vibration
X, Y, Z direction for 1 hour
0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X,
Vibration (malfunction)
Y, Z direction for 10 min
Shock
300 m/s
(≈ 30 G) in each X, Y, Z direction for 3 times
2
Shock (malfunction)
100 m/s
(≈ 10 G) In each X, Y, Z direction for 3 times
2
Mechanical: ≥ 10,000,000 operations
Relay life cycle
Electrical: ≥ 100,000 operations
(250 VACᜠ 5 A resistive load)
Ambient temperature
-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
LE3SA
LE3SB
MULTI time, Power ON Delay
≤ 100 ms
Power ON Start
-
-
-
Time limit
Time limit DPDT
SPDT (1c) +
(2c)
Instantaneous
SPDT (1c)
250 VACᜠ 3 A, 30 VDCᜡ 3 A
resistive load
≤ ± 0.01% ± 0.05 sec
≈ 105 g
LE3SA
LE3SB
AC: 3.3 VA, DC: ≤ 1.5 W
Electrical: ≥ 100,000 operations
(250 VACᜠ 3 A resistive load)
Input Connections (LE3S)
■ No-voltage (NPN) input
• Solid-state input
Sensor
(NPN open collector output)
LE3S
+ V
INHIBIT
START
OUT
RESET
Q1
GND
0 V
Q1-2: operates when it is ON.
• Contact input
LE3S
INHIBIT
START
RESET
S1
0 V
Use reliable contact enough to flow 5 VDCᜡ 1 mA
S1 (micro switch, push button switch, relay contact): operates when it is ON.
Output Operation Mode
■ LE3S
mark - START signal: continuously ON → time starts and output operates.
mark - START signal: though the one-shot input is occurred time starts and output
operates. (one-shot input signal: ≥ 20 ms)
Initial status: UP mode - Display value 0, output OFF
DOWN mode - Displays the setting time, output OFF
If the setting time is '000', the control output does not switch to ON.
The input time of output operation mode D, E: ≥ 100 ms
• T : setting time
• T = T1 + T2 + T3, T > Ta + Tb
A
T
POWER
START
RESET
RELAY OUT
①
Setting time
UP
0
Setting time
DOWN
0
1. START signal: continuously ON → Time starts
2. Position ① - progressing time = setting time → Output: ON, display value: Hold
3. Position ② - RESET signal: ON → Initial status
4. Position ③ - RESET signal: OFF → Time progress
5. Position ④ - START signal: OFF (output OFF status) → Display value: return to the initial status
B
T
POWER
START
RESET
①
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
1. START signal: continuously ON → Time starts
2. Position ① - progressing time = setting time → Return the output, display value: Hold
3. Position ② - RESET signal: ON → Display value: return to the initial status
4. Position ③ - START signal: OFF (output OFF status) → Display value: return to the initial status
C
T
T
POWER
START
RESET
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
1. START signal: ON → Time starts
2. Progressing time = setting time → Output: ON, display value: Hold
3. RESET signal: ON → Return to the initial status
4. Position ① - Recognizes the first START signal
5. Position ② - START signal: ON (unnecessary for continuous input) → Time progress
Sensor
(NPN output)
LE3S
+ V
INHIBIT
START
R
L
OUT
RESET
Q2
GND
0 V
T
Ta
T
②
③
④
T
Ta
T
②
③
Ta
T
T
①
②
Ta