Autonics ARD-A Series Посібник - Сторінка 7
Переглянути онлайн або завантажити pdf Посібник для Системи вводу/виводу Autonics ARD-A Series. Autonics ARD-A Series 10 сторінок. Devicenet remote i/o analog, terminal block type
Також для Autonics ARD-A Series: Посібник з експлуатації (4 сторінок)
ARD-A Series
Functions
Model
Com. speed auto-recognition
Network power voltage monitoring
Unit power on total time monitoring
Unit comment
Last maintenance data stored
Scaling
I/O comment
Adjustment gradient
Adjustment offset
Input conversion points setting
Input digital filter
Peak/Bottom hold
Disconnected cable detection
Input comparison
Hysteresis
Output setting for error
Communication speed auto-recognition
It recognizes communication speed when connecting
master. Communication speed is able to change only from
master unit.
After changing communication speed, re-supply the
network power to apply the changed communication
speed.
Network power voltage monitoring
network power voltage is lower than the set value, the
● If
network power voltage drop flag bit of Status bit is ON.
It can be read by Configurator or Explicit message.
●
Set monitoring voltage by Explicit message at Network
Power voltage (Set Value) of Application Object.
Setting range: 0 to 255
●
(factory default: 12V, Allowable range: ±1V)
※ Min. supplied power is 12V for ARD unit.
If network voltage is lower than 12V, the contents of
Explicit message reading is not guaranteed.
Unit power on total time monitoring
●
When total time for supplying power to the unit
becomes the SV, Threshold Run Hours Flag bit of
Status Bit turns ON. It can be read by Configurator or
Explicit message.
Set the time by Explicit message at Threshold Run
●
Hour of Application Object.
Setting range: 0 to 429,496,729 hours
●
(factory default: 876,000 hours),
Measured unit: 0.1 hours (6 minutes)
Unit comment
● You can set the comments for the unit (product
description) on network. It can be read by Configurator
or Explicit message.
● Set comment by Explicit message at Unit Comment of
Application Object.
● Setting range: max. 32 characters
X-30
ARD-AI04
(input model)
-
Last maintenance date
●
It saves the last date of maintenance. It can be read/
written by Configurator or Explicit message.
Set maintenance date by Explicit message at I/O Last
●
Maintenance Data Setting of Analog Input Point Object.
E.g.) Data: 0x07DB020E→07DB (2011), 02 (Februray),
0E (14th)
Input conversion points setting
● Conversion cycle is changed by the number of points
(point, channel).
(conversion cycle: 1ms/point, when using 4 points,
it is 4ms). It can be read/written by Configurator
or Explicit message. After changing the number of
conversion points, re-supply the network power.
● Set the number of conversion points by Explicit
message at Number of AD Conversion Points Setting
of Analog Input Point Object.
● Setting range:
1 to 4-point
conversion cycle: 1ms/1-point
Display scale
● Set high/low-limit scale value of analog input or output.
It can be read by Configurator or Explicit message.
Function Choice
: Scaling Flag bit ON
Default
Scaling Type
Scaling
: Default Scaling
(factory default)
Function Choice
: Scaling Flag bit
None
OFF
Scaling
Scaling Type
: Default Scaling
Function Choice
User
: Scaling Flag bit ON
Scaling
Scaling Type
: User Scaling
ARD-AO04
(output model)
-
-
-
-
-
-
(factory default: 4-point),
It is set as 1,000 per 1V (mA).
In case of 1-5V, 4-20mA, it is
applied from over min. allowable
range 0.8V (800), 3.2 (3,200).
The below input value is break
detection. It outputs as min.
allowable range.
It is set as default value 0 to
16000 (-8000 to 8000).
(0-5V, 1-5V, 0-10V, 4-20mA,
0-20mA: 0 to 16000, -5-5V, -10-
10V: -8,000 to 8,000 )
Set high/low-limit value to apply
at 'Scaling Point 0%' and 'Scaling
Point 100%'.
Setting range: -28,000 to 28,000