Galvin Engineering CliniMix Lead Safe 100.00.71.00 Інструкція з монтажу виробу - Сторінка 4
Переглянути онлайн або завантажити pdf Інструкція з монтажу виробу для Сантехнічний виріб Galvin Engineering CliniMix Lead Safe 100.00.71.00. Galvin Engineering CliniMix Lead Safe 100.00.71.00 18 сторінок. Hob mounted thermostatic progressive basin mixer - lever
6.0
INSTALLATION
®
The CliniMix
Thermostatic Progressive Mixing Valves must be installed using the appropriate Standard,
Code of Practice and legislation application to each state and following the details outlined in this section.
®
The CliniMix
Thermostatic Progressive Mixing Valves must be installed by a licensed plumber, or where
applicable, a licensed plumber who has undertaken T.A.F.E. training in Thermostatic Mixing Valves.
Note: To effectively control microbial hazards during system design, installation, commissioning and
maintenance, the requirements outlined in AS/NZ3666 and local legislation shall be adhered to.
If the valve is not installed correctly then it will not function correctly and may put the user in danger. It may
also void the warranty of the valve.
Prior to the installation of the valve, the system must be checked to ensure that the system operating
conditions fall within the recommended operating range of CliniMix
If the hot water supply temperature is greater than 90° Celsius, the valve may be damaged. If the temperature
of the hot water will rise above 90° Celsius a suitable temperature limiting valve must be fitted to the hot water
supply, prior to the inlet fittings. This temperature limiting valve must be installed as per the manufacturer's
instructions. It is important that both inlet dynamic supply pressures are 500kPa or less. If either supply
pressure exceeds 500kPa then a suitable pressure reducing valve must be fitted prior to the inlet control
valve to reduce the pressure to an acceptable limit.
These pressure reducing valves must be installed as per the manufacturer's instructions. To achieve optimum
performance from the valve it is recommended that the inlet pressures are balanced to within 10% of each
other.
The water quality conditions should be checked to ensure they do not exceed the limits as listed in AS3500.4,
Section 3.7.1. If they do exceed these limits, then it will be necessary to install a water softener or water
treatment device.
INSTALLATION COMPLIANCE: Galvin Specialised products must be installed in accordance with these
installation instructions and in accordance with AS/NZS 3500, the PCA and your local regulatory requirements.
Water and/or electrical supply conditions must also comply to the applicable national and/or state standards.
Failing to comply with these provisions shall void the product warranty and may affect the performance of the
product.
6.1
MOUNTING DETAILS
1. If the mounting hole does not already exist, mark
out and cut the hole in the bench/trough (see
section 4.0).
®
Progressive Thermostatic Mixing Valve.
2. Fit the tap to the basin and attach using the 'C' washer
and nut. Ensure the rubber washer is fitted between
the 'C' washer and ench. Adjust the tap to the
correct position and fully tighten the nut. Make sure
the O-ring in the base has not dropped out and is in
contact with basin top.
4
st
Version 2.1, 31
July 2020 , 4 of 18