Merlin 1000Si
3.6

Fan switch integration

There is the facility to connect a Fan Switch (FS1 or FS2 sold separately).
The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin
1000Si is 'ON' and turns the power off to the fan(s) when the key switch on the Merlin 1000Si is in
the OFF position. There is a dip-switch located inside the facia of the Merlin
1000Si labelled [EM SEL].
This is factory set to 'OFF' which instructs the 1000Si to shut down the fan(s)
and gas supply on activation of the emergency shut off button(s).
Upon installation, this can be switched to 'ON' - this will instruct the system to
leave the fans on and only shut off the gas supply on activation of the
Emergency shut off button(s).
Note: This option is not available if Fan Switch is not installed.
3.7

Auto reset

The Merlin 1000Si has an auto reset feature.
There is a dip-switch located on the inside facia of the Merlin 1000Si labelled
[AUTO RESET]. This is factory set to 'OFF'. When the power is restored after the
power cut, the panel has to be restarted manually.
Upon installation, this can be switched to 'ON' if required - this will instruct
the system to restart automatically when power is restored after the power
cut.
3.8

Gas fill and prove time

Gas fill and prove times are adjustable.
There are two dip-switches located on the inside facia of the Merlin 1000Si labelled [FILL TIME]
and [PROVE TIME]. They are factory set to 'OFF'.
FILL TIME is the amount of time the gas valve is open to fill the gas line.
Off – 5 seconds
On – 10 seconds
PROVE TIME is the amount of time the system tests the gas line for any leaks.
Off – 30 seconds
On – 50 seconds
Once the settings have been changed please remove mains power for 10 seconds.