3. Testing
Once the drinking tap has been installed and tested for leaks, the water height must be adjusted to
suit the available pressure.
TROUBLESHOOTING
PROBLEM
Inconsistent flow
Water is not flowing from tap
Continuous flow
Rate of flow inadequate
Button hard to press
CAUSE
Blocked top assembly
Water is turned off
Blocked flow restrictor
Top assembly loose or internally
obstructed or damaged
The flow regulator screw may
not be adjusted correctly
The mains pressure may be too
great
Version 2, 16 August 2017, Page 3 of 4
RECTIFICATION
Remove top assembly and clean
Turn on water
Remove restrictor and clean
Remove top assembly, clean with water
and re-grease spindle if required
Remove blanking screw and adjust flow
regulating screw as described
Reduce to below 500kPa (70PSI).
Regrease spindle if required