aguilera electronica AE/SA-OPI Технічний посібник - Сторінка 2
Переглянути онлайн або завантажити pdf Технічний посібник для Димова сигналізація aguilera electronica AE/SA-OPI. aguilera electronica AE/SA-OPI 2 сторінки. Algorithmic optical smoke detector
WIRING SCHEMATIC
Assembly
The base of the detector can be
mounted directly on false ceiling surfaces, or on electric connection boxes s haped
octagonally (75mm, 90mm or 100mm), round (75mm) or square (100mm), with no need for a mechanical adapter.
Wiring
Disconnect the supply voltage of the detection loop before installing the detector base.
To connect the positive input of the detection loop to the + terminal (positive input of the detection loop).
¡
Connect the negative input of the detection loop to the - terminal (negative input of the detection loop).
¡
If a remote action indicator is to be installed, connect the positive of the indicator to the +C terminal or positive of
¡
auxiliary supply and the negative to the R terminal.
AUXILIARY SUPPLY
INDICATOR
ALGORITHMIC LOOP
The action indicator can be fed from the detector itself, taking into account the total consumption of the loop, or by means
of an auxiliary supply.
If an auxiliary supply is used, the negative of the auxiliary supply should be joined to the negative of the algorithmic loop.
Ae-man-838-0.0 v1.0
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Tel.: 91 754 55 11 Fax.: 91 754 50 98 www.aguilera.es
INDICATOR
TECHNICAL MANUAL
Installing the detector
Position the detector on the base of the detector,
§
aligning the marks as indicated in the figure.
Rotate the d etector gently clockwis e until it is
§
well coupled.
After installing all the detectors, reconnect loop
supply voltage.
PRECAUTIONS
To prevent contamination of the detector, and the resulting loss of guarantee, keep the protective cover in place
§
until the area where the detector has been installed is clean and dust-free.
The protective cover does not ass ure complete protection against all types of dust or penetration b y foreign
§
substances, for which reason r emoval is recommended of the detector from the base if
(painting, sanding,...) are to be carried out, which can produce dust in suspension.
§
The detector should not be pai nted. The painting can bl ock the air inl ets to the optical cham ber and alter its
operation and sensitivity.
The protective cover should be removed before starting up the system.
§
VERIFICATION OF OPERATION
The detectors must be tested after installation and undergo periodic maintenance.
Before carrying out the operating tests, notify to the competent authority that maintenance tasks are being carried out
in the fir e detection system, and m ake sure that all the e vacuation, operation and trippi ng functions for automatic
extinguishing are disabled.
§
When removing the detector from the base, the area should be put in the fault state. If this does not take place,
check the wiring of the detector base, and that it is correctly programmed in the Algorithmic Panel.
§
Check that th e detector is working, by observing that it em its green colored flashes every 10 s, provided this
function has not been
inhibited individually from the detector i tself, or generally from the Algorithm ic Fire
Detection Panel. If the flashi ng is not inhibited and the detector do es not em it them, this m eans it has failed or
the wiring is faulty.
§
Activate the detector b y applying detector test aerosol. When sufficient sm oke has entered the cham ber, the
detector will go to the alarm state and activate the red LED in fixed mode.
§
If we have connected a remote action indicator, it will also light. If it does not do so, check the wiring.
The detectors that have not passed the operating tests should be replaced and repaired.
When the tests have been completed, reconnect the evacuation, operation and extinguishing functions, and notify the
competent authority that the fire detection system is again in service.
Ae-man-838-0.0 v1.0
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Tel.: 91 754 55 11 Fax.: 91 754 50 98 www.aguilera.es
BASE
1º: ALIGN THE DE TECTOR
WITH THE MARK ON THE
BASE AND INSERT THE
2º: ROTATE THE DETECTOR 30º
DETECTOR IN THE BASE
LED
construction activities