Airflow DUPLEXVENT DV145SE Інструкції з експлуатації, технічного обслуговування та технічні вказівки - Сторінка 6
Переглянути онлайн або завантажити pdf Інструкції з експлуатації, технічного обслуговування та технічні вказівки для Вентилятор Airflow DUPLEXVENT DV145SE. Airflow DUPLEXVENT DV145SE 17 сторінок. Low-energy ventilation unit with heat recovery and demand-controlled automatic melting
3.26
Adjusting fan on the supply air side
DC fan, supply
100%
3.27
Adjusting fan on the extract air side
DC fan, exhaust
100%
4.
Week-clock control
4.1
Week programme programming
The week programme can be used to set the desired fan speed (base fan
speed) and supply air temperature for each hour of the day on seven days
a week. The week programme overrides manual adjustments.
Carbon dioxide and humidity adjustment can increase fan speed but never
decrease it below the base fan speed set in the week programme.
Example: Monday
It is the intention to decrease fan speed to speed 2 and supply air tempera-
ture to 17 ºC between 07:00 (7 a.m.) and 16:00 (4 p.m.). After that, fan
speed is raised to speed 4 and supply air temperature to 20 ºC. For the
evening, fan speed is boosted to speed 6 between 19:00 and 21:00 (7
p.m. and 9 p.m.), after which fan speed is lowered back to 4.
STARTING POINT
d
hr
sp tmp
1
0
N
N
Exit
Cursor
d
Day 1...7
1 = Monday, 2 = Tuesday etc.
h
Hour 0...23
sp. Fan speed 1...8
Temp Supply air temperature
10...30°C
Exit Save the setting and exit
N
No change to previous hour setting
d
hr
sp tmp
1
7
2
17
Exit
d
hr
sp tmp
1
16
4
20
Exit
d
hr
sp tmp
1
19
6
N
Exit
d
hr
sp tmp
1
21
4
N
Exit
Similar changes have to be made separately for each day. Finally, exit the
programming mode by selecting Exit. If you wish, you can erase the week
programme as indicated in Section 3.6. You can then start programming
from the start. You can see the settings programmed by choosing a day and
by scrolling the hours with the + or – button.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack
of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand
Cleaning and user maintenance shall not be made by children without supervision.
6
DV145SE
OPERATING INSTRUCTIONS FOR CONTROL PANEL
The desired adjustment value for the
supply air fan is selected with the +
and – buttons. The rotation speed of
the supply air fan can be decreased
by decreasing the percentage.
The desired adjustment value for the
extract air fan is selected with the +
and – buttons.
The rotation speed of the extract air fan
can be decreased by decreasing the
percentage.
Move the cursor with the arrow keys and
change values with the + and – buttons.
Note that to exit and save when the
programming is fi nished, move the cursor
below the word Exit and press + or –.
Changes in fan speed (Sp.) and supply
air temperature (Temp.) are only made
for the hours desired; in other cases, use
N (no change to previous).
Monday (d = 1), 07:00 (h = 7),
fan speed 2 (sp = 2), supply air
temperature 17 °C (tmp =17).
Move the cursor to the following hour.
Monday (d = 1), 16:00 (h = 16),
fan speed 4 (sp = 4), supply air
temperature 20 °C (tmp = 20).
Move the cursor to the following hour.
Monday (d = 1), 19:00 (h = 19),
fan speed 6 (sp = 6), supply air
temperature no change (tmp = N).
Move the cursor to the following hour.
Monday (d = 1), 21:00 (h = 21),
fan speed 4 (sp = 4), supply air
temperature no change (tmp = N).
Move the cursor to the following hour.
Children shall not play with the appliance.
3.28
Fan speed level adjustment
Speed 1 level
15%
If for instance speed 3 is 30%, speed 2 cannot be increased to more
than 29% and speed 4 cannot be decreased below 31%.
The fan stops when the setpoint is 14% or lower. The adjustment is made
with the + and – buttons. There are 8 displays, one for each fan step.
3.29
Moving to Operating menu
To Main menu
press + and –
4.2
Adjusting time
day
hour
min
1
15
30
Cursor
D
Day 1...7
1 = Monday, 2 = Tuesday etc.
H
Hour, 0...23
M
Minutes, 0...60
Exit Save the setting and exit
5.
Factory settings
Base fan speed
Maximum fan speed
Carbon dioxide adjustment (CO
Adjustment interval
Winter parameter A
Winter parameter B
Mode of melting
Maintenance reminder
Cell bypass
Cascade adjustment
Speed steps:
1.
2.
3.
4.
5.
6.
7.
8.
Humidity level (Rh level) setting
Switch type
Extraheater type
the hazards involved.
© Air ow • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
The desired fan speed level is adjusted
from the menu. Adjustment range is
0–100%. However, fan speeds limit
the adjustment range as follows:
To move back to the Operating menu,
press the + and – buttons simultaneous-
ly.
Move the cursor with the arrow keys and
change values with the + and – buttons.
Exit
Exit and save when the programming is
fi nished.
Monday (D=1), hours 15 (H=15), minu-
tes (M=30)
Time is maintained even though there is
a power failure. (See Section 1.1, fi gure
items 5 and 6).
= 1
= 8
) = 900 ppm CO
2
2
= 10 min
= 9 bars
= 3 bars
= heat recovery cell bypass
= 4 months
= 12 °C
= not in use
= 31 %
= 42 %
= 47 %
= 54 %
= 59 %
= 66 %
= 72 %
= 100 %
= automatic
= fi replace switch
= electric radiator