Green Brook Phoenix ELTSLED65NM Інструкція з монтажу та експлуатації - Сторінка 2

Переглянути онлайн або завантажити pdf Інструкція з монтажу та експлуатації для Освітлювальне обладнання Green Brook Phoenix ELTSLED65NM. Green Brook Phoenix ELTSLED65NM 2 сторінки.

4. Bring the cable into position and make the correct electrical connections as follows:
Note: The ELTSLED65NM uses screwless terminals.
Class I. This product must be earthed.
Terminal (L):
This is the live supply to the charging circuit and must be permanent
and unswitched.
Terminal (
E):
This is for the earth and must be connected.
Terminal (N):
This is the neutral supply and must be permanent.
Colour code:
Brown=Live Blue=Neutral Green/Yellow=Earth
Conductor Space Size 1.0mm
Ensure that no strands of bare wire have escaped the terminals.
5. Mark the battery cell pack with the date of installation and connect the battery.
6. Refit the front cover, taking care to ensure that no wires are trapped and that all fastenings are
secure.
7. To adjust the position of the lamp heads, loosen the axis screws before positioning so as not to cause
excess strain on the lamp fixings.
WARNING
The battery cell pack must be
ONNE TED before the mains is switched on.
Failure to comply with these installation instructions may result in irreparable damage to the main circuit.
DO NOT HIGH-VOLTAGE INSULATION TEST THIS UNIT, OR THE LIGHTING SYSTEM WITH THIS UNIT CONNECTED.
Please note once unit is installed the battery should be kept charged, failure to do so will reduce the
battery life.
When unit is commissioned the battery label should be dated with the commissioning date and record
sheet completed for the first test. Failure to do this may invalidate the warranty.
COMMISSIONING & TESTING
Switch on the mains supply, check that 'Charge ON', 'Lamp 1' and 'Lamp 2' green LED indicators are
lit.
Allow a brief time for initial partial charging and then isolate the permanent live supply by removing the
fuse from the fused spur box. Check to ensure the lamps are illuminated from the battery cell pack
supply. After a further 60 hours on a continuous charge, and only at a safe and appropriate time, mains
failure should be simulated to ensure that full duration rating is achieved. Thereafter the recharge time is
24 hours.
Function of LED Indicators
1.
Auto test indicator
2.
Failure/charging indication
3.
Lamphead 1 indicator
4.
Lamphead 2 indicator
Audible Alarm
• Battery failure:
One repeated beep
• Illumination Failure:
Repeated two beep cycle
• Auto test failure:
Repeated three beep cycle
Auto Fault Monitoring
When connected to the mains supply and a system fault is detected, the audible alarm will sound
continously for the first 10 minutes and the failure/charging indicator will flash. After 10 minutes the
alarm will beep once every minute for the next hour. After the first hour it will beep every twenty minutes
upto twenty four hours. After this the alarm will cease and the fault indicator will flash only.
Auto-test Switch
• Manual Test: Press the button on the PCB for 3 seconds, the emergency light will come on for
5 minutes to check illumination.
- 2.5mm
Solid or Stranded.
2
2
1.
2.
3.
4.
Auto-test Switch
• Manual Test: Press the button on the PCB for 3 seconds, the emergency light will come on for
5 minutes to check illumination.
• Auto Test: Press the button for 1 second, this initiates the 'Auto Test' sequence. The emergency
light will light automatically once every 90 days for test duration of 1 hour. If the fitting fails to
light for 1 hour the audible alarm will give a three beep sequence as mentioned in the audible
alarm section above. If the 1 hour test is satisfactory the fitting will return to normal operation.
Servicing should only be carried out after the luminaire has been made electrically safe.
Lamps should be replaced at set intervals for maximum system integrity, use only lamps of the correct
type and rating and follow the lamp manufacturers instructions.
Cleaning should be carried out at regular intervals to ensure that dirt does not accumulate to an extent
that will impair the electrical and / or thermal safety of the luminaire. Regular cleaning will also ensure
that the optical performance is maintained.
Battery packs should be replaced when the luminaire fails to meet its rated duration, regardless all
batteries must be replaced after 4 years service.
The disposal of components from the luminaire may require consultation with local authorities.
The disposal of batteries is subject to Local Authority Regulations, and the By-Laws Department for
disposal of toxic waste should be consulted for specific guidance. Battery cell packs must not be
incinerated. Do not dispose with household waste, subject to conditions in the WEEE directive.
ROUTINE INSPECTION & TEST PROCEDURE
All tests should be undertaken during daylight hours at times of minimum risk and be in accordance with
the recommendations of BS 5266 Part 1
DAILY - Check that the three green LED battery charging / lamp failure indicators are illuminated.
MONTHLY - In addition to the daily check, a functional test through simulation of mains supply failure
should be carried out to confirm lamps are illuminated from the battery cell pack supply. This test need
only be approximately 30 seconds. It should not exceed one quarter of the rated luminaire duration.
SIX - MONTHLY - In addition to the monthly test, the lamps should be illuminated from the battery cell
pack supply for a continuous period of at least one hour.
THREE - YEARS - In addition to the monthly tests the lamps should be illuminated from the battery cell
pack supply for the full rated duration of the luminaire. (180 minutes).
ANNUALLY THEREAFTER - As above, i.e, Check that the luminaire operates for the full rated duration (180
minutes).
At the end of each test period the mains supply should be restored and a check made to ensure that
all three green LED battery charging/lamp failure indicators are illuminated.
MAINTENANCE