Electrical connections - GAT NET.Controller S 7000
GAT NET.Lock 7000 connections
GAT NET.Controller S 7000
1
2
3
4
to the GAT NET.Lock 7000 locks
Power and network connections
GAT NET.Controller S 7000
From master controller or from
previous GAT NET.Controller S 7000
GAT NET.Lock 7000 connections
The locks are connected using a GAT NET.Lock Cable 5m (Part No.
734430). The 5 m cable can be extended using the GAT NET.Lock Cable
Extension 3m (Part No. 810021) or to max. 10 m using the GAT NET.
Lock Connector (Part No. 442123) and another GAT NET.Lock Cable 5m.
The numbers on the GAT NET.Controller S 7000 determine the channel
assignment for the locks.
The GAT NET.Lock 7000 locks must not be connected to the GAT
SMART.Controller S 7000!
Network connections
- RS 485 bus connection to slave controllers via RJ 45 jacks.
On the GAT NET.Controller S 7000, connect the incoming RS 485 line
(server/master side) to the "RS 485 IN" socket and the outgoing RS 485
line (to next slave controller) to the "RS 485 OUT" socket.
Recommended cabling
RS 485: min. CAT 5 (STP), 200 m maximum cable length per line.
LED signaling
RS 485
IN
yellow
- RS 485 IN (yellow): Connection to the master controller
- RS 485 IN (green): RS 485 communication active
- LED 1 (blue):
Lock action
- LED 2 (green/red): Status information (see manual)
Reset and mode buttons
- RESET:
1. Reset of controller (see manual)
2. Delete configuration = reset to default (see manual)
- MODE:
Perform automatic antenna adjustment (see manual)
Valid from September 15
2015 • Technical data subject to modification without notice!
th
4
DB_GAT-NETCONTROLLER7000--EN_23.indd • Part No.: 573835
5
6
7
8
9
10
11
RS 485
RS 485
IN
OUT
Power
Power supply GAT NET.Power Supply
(or power plug - see description below)
To the next GAT NET.Controller S 7000
RS 485
OUT
Power
green
12
13
14
15
16
17
18
Note: The GAT NET.Controller S 7000 F/ISO Light has 12 lock connection ports
Power supply
RS 485
RS 485
IN
OUT
Power
There are two possibilities for power supply:
1. A power supply is connected to every GAT NET.Controller S 7000 in a
RS 485 line.
2. A power supply is connected to a few controllers that forward power on
to the remaining controllers in the RS 485 line. For the controllers that
are not directly supplied, a power plug (see order information) must be
plugged into the "Power" socket.
Note: A power supply must always be connected to the first slave
controller. If five or more slave controllers are used, the fifth
controller must also be supplied in addition to the first controller.
GAT NET.Controller S 7000
Power for the RS 485 line must be forwarded in the correct
direction. Use the „RS 485 OUT" socket to continue supply to
the next controller as shown above.
19
20
21
22
23
24
Power is connected to the MOLEX
socket labeled "Power". Use the supplied
power supply unit (see technical data).
Supply
From master controller
RS 485
OUT
IN
Power
Plug
OUT
IN
www.gantner.com
RS 485
Supply
OUT
IN