Kohler 1.4BEOR-12V Операція - Сторінка 23

Переглянути онлайн або завантажити pdf Операція для Портативний генератор Kohler 1.4BEOR-12V. Kohler 1.4BEOR-12V 44 сторінки. Heavy duty truck mobile generator sets

WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on the
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.
cause severe injury or death.
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause
severe injury or death. Do not operate the generator set with
the air cleaner removed.
The engine and generator set may use both American
Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
See the Safety Precautions and Instructions at the
beginning of this manual before attempting to service,
repair, or operate the generator set. Have an authorized
Kohler distributor/dealer perform generator set service.
Engine Service. Perform generator set engine service
at the intervals specified by the engine operation
manual.
TP-6687
9/10
generator set.
Accidental starting can
Before working on the

Section 5 General Maintenance

Generator Set Service. Perform generator set service
at the intervals specified by the generator set operation
manual.
If the generator set operates under dusty or dirty
conditions, use dry compressed air to blow dust out of
the alternator. With the generator set running, direct the
stream of air in through the cooling slots at the alternator
end.
Routine Maintenance. Refer to the following generator
set service schedule, the engine service schedule, and
the runtime hours shown on the 1.4BEOR Remote
Control Unit to determine when to schedule routine
maintenance. Service generator sets that are subject to
extreme weather or dusty or dirty conditions more
frequently.
Service Log. Use the Operating Hour Service Log
located in Appendix B to document performed services.
Service Schedule. Perform maintenance on each item
in the service schedule at the designated intervals for
the life of the generator set. For example, an item
requiring service every 100 hours or 1 month also
requires service after 300 hours or 3 months, 500 hours
or 6 months, and 1000 hours or 1 year.
5.1 International Lubricant
Specifications
The
lubricant
specifications
performances and procedures that the lubricants need
to successfully respond to in several engine testing and
laboratory analysis so as to be considered qualified and
in conformity to the regulations set for each lubrication
kind.
A.P.I.
American Petroleum Institute
MIL
Engine oil U.S. military specifications released
for logistic reasons
ACEA European Automobile Manufacturers
Association
5.2 ACEA Regulations, ACEA
Sequences
5.2.1

Light Duty Diesel Engines

B1 = Low-viscosity for frictions reduction
B2 = Standard
B3 = High performance (indirect injection)
B4 = High quality (direct injection)
Section 5 General Maintenance
define
testing
23