a-TroniX 9887579 Посібник з монтажу та експлуатації - Сторінка 11
Переглянути онлайн або завантажити pdf Посібник з монтажу та експлуатації для Контролер a-TroniX 9887579. a-TroniX 9887579 16 сторінок. Mppt solar charge controller
Machine Translated by Google
operation manual
MPPT solar charge controller X45/10
8.50°C Charge (Lithium)
The 0°C charge can be set to "Yes", "No", or "Slow".
If the temperatures are higher than 0°C, the normal charging mode is used. However, when
temperatures are below 0°C, the following applies:
charge mode
Yes
Slow
no
8.6 Day/Night Threshold
and day/night delay
Based on the open-circuit voltage of the solar system, the charge controller recognizes day
and night. The day/night threshold can be adjusted depending on the lighting conditions.
Threshold setting range: 3.0 to 8.0 V.
The threshold can be delayed by up to 30 minutes using the day/night delay.
The load shedding threshold voltage is 1V higher than the setting data.
This means that the load will be cut off when the solar voltage is between 4.0V to 9.0V.
The controller automatically adjusts the threshold voltage.
On the first night, the load will have no power. 24 hours later, the controller automatically
adjusts the setting to deliver power the following night.
02/2022
Battery can be charged normally
Max. charging current is 20% of the rated current
Battery cannot be charged
charge
page 11