AB Quality PowerFlex 400 Frames D-H Сервісний бюлетень - Сторінка 8
Переглянути онлайн або завантажити pdf Сервісний бюлетень для Контролер AB Quality PowerFlex 400 Frames D-H. AB Quality PowerFlex 400 Frames D-H 12 сторінок. Main control board
8
PowerFlex 400 Frames D-H Replacement Procedure for Main Control Board
Publication 22C-SB003A-EN-P – August 2008
3. Remove the plastic tray together with the main control board.
4. Place the new plastic tray with the new main control board where the old
tray was.
The main control board should fit the plastic tray snugly.
IMPORTANT
5. Place the four screws back in to secure the plastic tray.
Torque to about 0.9...1.1 N-m (8.0...9.7 lb.-in).
For Frame D, use the four tapping 4*8 mm screws.
IMPORTANT
For Frames E-H, use the four M4*8 mm screws.