Aqua Logic DS-10-WCMD Посібник з монтажу та обслуговування - Сторінка 4
Переглянути онлайн або завантажити pdf Посібник з монтажу та обслуговування для Охолоджувач. Aqua Logic DS-10-WCMD. Aqua Logic DS-10-WCMD 9 сторінок. Delta star water-cooled marine duty in-line water chillers
WARNING: DO NOT over tighten water fittings.
•
Mount chiller on a flat pad and away for water spray.
•
Give at least 1 ft all the way around unit for servicing.
•
Install evaporator water inlet and outlet.
•
Install condenser water inlet and outlet.
•
Test water fittings for leaks.
•
Apply electrical power to the chiller.
•
Adjust the controller to the desired water temperature. (See "Operation and Programming")
•
Important:
Regulate condenser water until pressure on the pressure gauge reads between 115 to 125 PSIG for models
DS-4-WCMD thru DS-9-WCMD and 195 to 220 PSIG for model DS-10-WCMD. Check after 15 minutes of run time,
adjust the water flow (if needed) to the correct pressure.
Warning: This unit must have proper water flow rate both on the evaporator and
the condenser to operate correctly.
CHILLER SET-UP AJUSTMENTS
Copyright© 2016 Aqua Logic, Inc. Effective date of 1/2016
4