Features and Benefi ts
Outlet level, phase level, and strip level current/voltage/power metering with threshold/alert capabilities*.
Provides preemptive notifi cation of any impending overload issues before they occur, and simplifi es the
task of installing new equipment.
Capability
to remotely switch outlets through onboard web interface, DSView 3 management software (Not
available on PM2000).
Allows power to hung up IT equipment to be recycled, turned on or turned off
remotely for faster resolution time.
On board web interface.
Can be installed for direct access right out of the box or it can be confi gured
as part of a larger integrated solution using the DSView 3 software.
IP and Serial interface options.
Options to install by connecting directly to the network or save IP
connections by using the serial interface to connect directly to Avocent appliances already connected
to the network.
Daisy chaining.
Saves the number of IP addresses or console / KVM ports that are required to
manage all power distribution needs.
Integration with DSView 3 software.
simplifi es mapping of outlets to servers and other equipment to reduce and minimize power cycling the
wrong equipment.
Integration with DSView 3 Power Manager.
consumption, capacity, and cost to understand what issues exist and to make more informed
decisions in the future.
Electronic Overcurrent Protection.
that is activated in the event of minor overloads. During such events, outlets are turned off fi rst
instead of the primary overcurrent protection (OCP) tripping.
Sequential Startup.
Protects integrity of all upstream electrical infrastructure by staggering the inrush
current draw of all plugged in devices.
Internal temperature sensor and two optional external sensors.
environmental factors at several different points within the rack.
PM2000
PM3000
Part Numbers
Part Numbers Description
Ordering Details
North America
PM2001H-401
PM3001H-401
PM2002H-401
PM3002H-401
PM2005H-403
PM3005H-403
PM2005H-404
PM3005H-404
PM2001V-401
PM3001V-401
PM2002V-401
PM3002V-401
PM2005V-403
PM3005V-403
PM2005V-404
PM3005V-404
International
PM2003H-401
PM3003H-401
PM2004H-401
PM3004H-401
PM2005H-406
PM3005H-406
PM2003V-401
PM3003V-401
PM2004V-401
PM3004V-401
PM2005V-406
PM3005V-406
External Sensors
PMHD-THS
Temperature, Humidity, Air Flow and dry contact combo sensor
PMHD-TS
Temperature only sensor
Note: PM2000 models include per outlet metering capabilities
PM3000 models include per outlet metering and switching capabilities
AMP values listed on the North American models are rated at 80% based on national electric codes.
*(Note- measurement resolution +/- %5)
Single interface for management of IT equipment and IPDUs
Track historical trends to measure and monitor IT power
Electronic Overcurrent Protection is an added layer of protection
These sensors can measure
Horizontal 1-ph 24A 200-240V with L6-30, 3 C19 ports
Horizontal 3-ph 24A 200-240V with L15-30, 6 C19 ports
Horizontal 3-ph 40A 200-240V with Hubbell® CS8365C, 6 C19 ports
Horizontal 3-ph 48A 200-240V with IEC 309 60A, 6 C19 ports
Vertical 1-ph 24A 200-240V with L6-30, 21 C13 & 3 C19 ports
Vertical 3-ph 24A 200-240V with L15-30, 21 C13 & 3 C19 ports
Vertical 3-ph 40A 200-240V with Hubbell CS8365C, 21 C13 & 3 C19 ports
Vertical 3-ph 48A 200-240V with IEC 309 60A, 21 C13 & 3 C19 ports
Horizontal 1-ph 32A 220/230/240V with IEC 309 32A, 3 C19 ports
Horizontal 3-ph 16A 380/400/415V with IEC 309 16A, 6 C19 ports
Horizontal 3-ph 32A 380/400/415V with IEC 309 32A, 6 C19 ports
Vertical 1-ph 32A 220/230/240V with IEC 309 32A, 21 C13 & 3 C19 ports
Vertical 3-ph 16A 380/400/415V with IEC 309 16A, 21 C13 & 3 C19 ports
Vertical 3-ph 32A 380/400/415V with IEC 309 32A, 21 C13 & 3 C19 ports
www.avocent.com/contacts
Specifi cations
Mechanical
Size: 17 x 8.272 x 1.719 in (horizontal),
2.2 x 66 x 3.15 in (vertical)
Weight: 7.3 lbs (horizontal without
power cord), 14.8 lbs (vertical without
power cord)
Environmental
Operating Temperature: 50 to 122 F (10
to 50 C)
Storage Temperature: -40 to 149 F (-40
to 65 C)
Network Connection
Number: 1
Type: 10/100/1000 Ethernet
Accessories Included
Rackmount kit, toolless mounting
hardware with vertical models and outlet
retention clips
Standards
Approved Agency:
UL, FCC, cUL, CE, VCCI, C-Tick, CB
Warranty
Two Year
PM3000
Intelligent Power Distribution Unit
Avocent, the Avocent logo, DSR and DSView are registered trademarks of
Avocent Corporation or its affi liates in the U.S. and other countries. All other marks
are the property of their respective owners.
Copyright © 2008. Avocent Corporation.
120 8-PM2K3K-DS-EN