STATUS LED STATE
Off
Power off.
Steady Green
Normal operation.
Green, 1 Flash
Device not calibrated.
Green, 2 Flash
Over Range Condition: Once calibrated the TA500-ECAT will
indicate an over range or under range condition by setting the
error code to 'Outside Cal Range'. The error is active once -20%
or 120% tension is exceeded - Action Required: To clear this error
the tension must be brought back into range, or a new calibration
will need to be performed to do so.
Red, 3 Flash
Wiring Error: Will alert until the load cells are wired correctly -
Action Required: Check wiring and retry. Check for loose wires
at the terminal blocks, check for shorts, and be sure the load
cells are connected. If the transducers need trouble shooting
– contact tech support for assistance. Overload Condition (LT
Transducer): Will intermittently alert if overload is reached -
Action Required: Check that the tension range does not exceed
the transducer load rating. Reduce wrap angle to reduce effective
net force exerted on load cell.
Red, 4 Flash
Excitation Failure or Wiring Error - Action Required: Check for
shorts in the transducer / load cell wiring. If the transducers need
trouble shooting – contact tech support for assistance.