Advanced programming

The tables on pages 12 to 14 give a summary of all programmable parameters for the MWS3A-AT-PRM Sensor.
Parameter Name
Default Value
For Device
Product ID
Automatically
assigned by the
device
Building Code
1
Lock
0
For Channel 1 (Switched Output)
Local Code
1
Sub Local Code(s) Not set
Area Code(s)
999
Circuit Number
1
Detection Mode
Presence
Output State
Set by Scene
Raise from off
1
Lower from off
1
Lux off period
0
Lux switching
1
enabled
Detector enabled
1
Detector inhibit
0
period
12
Range / Options
Description
1 to 999
A number used to uniquely identify each device within a range of
devices that are set to the same Local Code.
1 to 999
A number shared by all devices that belong to the same building or
system.
Enable (1) or disable
Lock the An-10 network. Prevents more devices joining the network.
(0)
1 to 999
A number corresponding to the Local Code of all devices to be
controlled by an associated input channel.
1 to 99
A number corresponding to the Sub Local Code of all devices to be
0 to clear
controlled by an associated input channel. Up to 20 Sub Local
Codes can be set for the switched output Channel 1.
1 to 999
A number corresponding to the Area Code of all devices to be
0 to clear
controlled by an associated input channel. Up to 32 Area Codes can
be set for the switched output Channel 1.
1 to 999
Sets the circuit number for this channel.
Presence or Absence
Presence mode allows the output to turn on when movement is
detected and off when movement ceases. Absence mode allows
the output to turn off when movement ceases, but must be manually
turned on first.
0-100%
The current output state of the channel, for example as set by a
0=off
Scene Select command.
Enable (1) or disable
Enables raise from off feature.
(0)
Enable (1) or disable
Enables lower from off feature.
(0)
0 to 999 in minutes
Number of minutes above the Lux Off level before a lux switching
(0=15 seconds)
decision is made.
Enable (1) or disable
Enables or disables the output channel to respond to lux switching
(0)
commands.
Enable (1) or disable
Enables the output channel to be controlled by detector occupancy.
(0)
0 to 255
Detector inhibit period in 100s of milliseconds (255 = 25 seconds).
Programming
Devices
UHS4