The following items are included with PSUs purchased separately:
one AC power cord (AC model)
one power cord retaining clip (AC model)
one Installation Guide
one warranty card
The following items are included with each FOM purchased separately:
one Installation Guide
one warranty card

Installing a Power Supply Unit

Warning All AC and DC versions of this equipment must be earthed.
Do not install an AC PSU and a DC PSU in the same switch chassis.
If you remove a PSU or FOM from the switch, immediately replace it or cover
the bay with a blanking panel. This prevents dust and debris from entering the
chassis and maintains proper airflow in the switch.
AC power supply unit specifications
Important information for service personnel:
CAUTION: double pole/neutral fusing
the rating of fuses FH101 and FH102 is 250 V, 5 A (AT-PWR01 only)
DC supply cable and power supply specifications
three-core cable is required
minimum core size: 3.3 mm
minimum cable rating: 600 V, 90 degrees Celsius
DC power supply specifications
40 to 60 V, 48 V nominal
supports either positive grounded or negative grounded operation
a 15 Amp certified/listed circuit breaker is required for circuit protection
2
(12 AWG) high strand count copper wire
Installation Guide