CPS Leak-Seeker LSCG Посібник із швидкого старту - Сторінка 12
Переглянути онлайн або завантажити pdf Посібник із швидкого старту для Вимірювальні прилади CPS Leak-Seeker LSCG. CPS Leak-Seeker LSCG 16 сторінок. Combustible gas leak detector
a. The LSCG will beep and vibrate once.
3. LSCG WILL AUTOMATICALLY CALIBRATE & START UP
a. Display will Count Backwards From 40 Seconds- During this time,
the gas sensor will heat up and the device will automatically
calibrate.
b. After 40 Seconds- LSCG will beep and vibrate once. The display
will show:
i. PPM Speedometer Scale (At Top Of Display): 0 PPM
ii. PPM Readout: 0 PPM
iii. LEL Readout: 0% (Lower Explosion Limit value)
iv. Max Readout: 0 (Lower Right Corner Of Display)
c. To Clear Any PPM & LEL Display Values On The Display During
Each Warm Up.
i. Press AUTOZERO Key- This will return PPM, LEL readings
to "0".
d. Battery Icon (Top Right Portion of Display)- Four "segments"
within the icon outline mean the battery is 100% charged.
Three segments mean the battery is 75% charged, etc.
e. If Entire LCD Flashes & Beeps- Sensor has failed and should
be replaced.
4. AFTER INITIAL START UP
a. Speaker & Vibration Alarm Icons Visible On the Display-
Both will be ON (visible in the upper LEFT) by default. These
indicate that the Audible and Vibration alarms will operate if
the LSCG detects a combustible gas. To turn either alarm
OFF, press one or both keys on the keypad.
a. APO (Auto Power OFF) Visible At Top Of Display -APO is the
default setting.
i. If "APO" Visible -The LSCG will turn OFF (to conserve the
battery) if device has NOT been used for 10 minutes. To
enable the LSCG to remain ON constantly, press the APO
key so that "APO" is not visible.
5. SET GAS CONCENTRATION
a. Use the Concentration Setting High/Low Key (H/L)
i. X10" (Low Concentration Scale: 10 To 1,000 PPM)- LOW is
the default sensitivity- "X10" will be visible on the RIGHT
SIDE of the display. "X10" means that any PPM value visible
(to its left) is to be multiplied by 10. 10 PPM is lowest PPM
"resolution". Example: If "5" is visible, 5x10 PPM = 50 PPM
being detected.
12