Location Requirements for the Hybrid Cooling Module:
1. Within 20 feet of the earth loop line set. Minimize refrigerant line lengths.
2. No more than 20 feet higher than the earth loop manifolds.
3. With proper clearances around the unit:
24 inches minimum on the two sides and back (coil side)
36 inches minimum on the front (fan side)
4. Away from windows, patios, decks, etc., where unit operation sounds may disturb the
occupants.
5. On a solid, level mounting pad. The mounting pad should extend a minimum of 2 inches
beyond the cabinet size of the Hybrid Cooling Module. The minimum pad size is to be
16 inches by 40 inches. The pad should NOT be in contact with or be an integral part
of the building foundation. The following DiversiTech Pads (or their equivalent) are
recommended. The standard pads are 2" thick. Local building codes may require a 3"
thick pad.
Model Number
®
Ultralite
UC2448-2
®
Ultralite
UC2448-3
®
Elite
EL3648-2
®
Elite
EL3648-3
6. Where conditions or local codes require the Hybrid Cooling Module to be attached to a
mounting pad or frame, tie down bolts should be used to fasten through the holes
provided in the Hybrid Cooling Module feet.
7. Elevate the Hybrid Cooling Module per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate water drainage of Hybrid
Cooling Module. Use snow stand in areas where prolonged freezing temperatures are
encountered.
Do NOT Locate the Hybrid Cooling Module:
1.
On brick, concrete blocks or unstable surfaces
2.
Near clothes dryer exhaust vents
3.
Near sleeping area or near windows
4.
Under eaves where water, snow or ice can fall directly in the unit
5.
Within clearance less than 2 feet from a second unit
6. Within the minimum distance the Hybrid Cooling Module can be installed from the
property line, where local zoning ordinances apply.
HCM-IMM (10/16)
Size, Inches
Comments
24 x 48 x 2
Fiber-cement construction
24 x 48 x 3
Fiber-cement construction
36 x 48 x 2
Plastic-drillable for securing unit
36 x 48 x 3
Plastic-drillable for securing unit
7