10. Voltage (as supplied)
11. Voltage (as supplied)
Plug and socket connection recommended to facilitate
accessibility for electrical safety tests.
Socket must be accessible after installation.
In the case of hard-wired connections, an all-pole mains
switch must be provided.
Contact gap: 3 mm. In the case of multiple units, main
switches should be properly labelled.
Supply cables should not be in direct contact with any source
of heat.
Installation must be CAT II grade.
Max. permissible supply fluctuation +/- 10%
Connection to electrical supply should be in accordance with
valid regulations and safety standards.
Equipotential
Pin with external thread, washer and nut provided
bonding and
with machine, size
protective earth
conductor
Connect equipotential bonding and protective earth
conductor!
Network/
The following machine interfaces are available for the
printer connection
transmission and printing of process data.
(optional)
Ethernet interface:
A RJ45 plug is available on the rear of the washer.
Install RJ45 socket in vicinity of machine. Cable supplied on
site.
Connections/installation must comply with IEC 60950.
Installation plan PG 8535
Version: 01.10.2010
Rated load
Fuse rating
Min. supply lead cross-section
Length of supply lead (H05(07)RN-F) without plug
Voltage
Rated load
Fuse rating
Min. supply lead cross-section
Length of supply lead (H05(07)RN-F) without plug
Rated load
Fuse rating
Min. supply lead cross-section
Length of supply lead (H05(07)RN-F) without plug
Voltage
Rated load
Fuse rating
Min. supply lead cross-section
Length of supply lead (H05(07)RN-F) without plug
V/Hz
3N AC 380/60
kW
6.7
A
3 x 16
mm²
5 x 2.5
m
2.3
V/Hz
3 AC 220/60
kW
6.7
A
3 x 20
mm²
5 x 2.5
m
2.3
V/Hz
3 AC 220/60
kW
6.7
A
3 x 20
mm²
5 x 2.5
m
2.3
V/Hz
3N AC 380/60
kW
6.7
A
3 x 16
mm²
5 x 2.5
m
2.3
M
8x1.25