Allmand MAXI HEAT 500IQ Посібник - Сторінка 5
Переглянути онлайн або завантажити pdf Посібник для Промислове обладнання Allmand MAXI HEAT 500IQ. Allmand MAXI HEAT 500IQ 19 сторінок.
SERIAL NUMBER 14-000001 AND UP
Burner Cycles On & Off
**Maxi Heat 500IQ has one burner that will begin to run and then shuts down for High Temp
Fault. ( Message appears on the IQ screen).**
❏ Each burner or both cycling on and off indicates that there is a possibility of
backpressure. Back pressure occurs when the flow of heat is restricted and not
moved which accumulates at the outlet or in the burner itself. Kinks in the ducting
can cause this issue. Make sure the ducting is straight with limited bends and no
elevated lifts or descending of the ducting.
❏ Check ducting for proper flow.
❏ Ensure the high limit sensor is working at the end of the outlet.
❏ Check the main blower fans connection and ensure it is turning on as needed.
Faulty connections or loss of power can cause a stall in fan operation which in
turn causes the heater to increase temperature.
❏ Make sure heat going into the area is ventilated so heat does not accumulate
and raises temperature to increase output.
M axi Heat 500IQ