Allmatic SCOR.AS Посібник - Сторінка 8
Переглянути онлайн або завантажити pdf Посібник для Блок управління Allmatic SCOR.AS. Allmatic SCOR.AS 8 сторінок. For barriers bevk 1 motor 24vcc
19. State of alarm of the control unit
If the flashing light blinks fastly or remains light on fix, it means that the control unit is in state of alarm. Any command is ignored until the resolution
of the problem.
Type of problem
Fast blinking of the flashing light
Flashing light still and lit
20. Problem solving
This paragraph intends to give some indications for solving the most common problems. Before proceeding, check that the LED present on the
panel are correctly on or off, according to the following diagram:
Step by step/Open
off
If one of more LED are not in the correct status check the corresponding input. In case exclude the external accessories bridging the related
inputs (photocell, stop, limit switch) with the common in case of normally closed contact.
Check the points in the following table:
Type of problem
On activating the open command, the wings do
not move.
On activating the open command, the wings
close.
Impossible to programme remote controls.
It is impossible to enter in wing stroke
programming mode.
The control unit is power supplied but the
automation doesn't move
During the learning, a wing stop before to reach
the total opening.
The automation moves only for one second and
then stops
GUARANTEE - In compliance with legislation, the manufacturer's guarantee is valid from the date stamped on the product and is restricted to the
repair or free replacement of the parts accepted by the manufacturer as being defective due to poor quality materials or manufacturing defects.
The guarantee does not cover damage or defects caused by external agents, faulty maintenance, overloading, natural wear and tear, choice of
incorrect product, assembly errors, or any other cause not imputable to the manufacturer. Products that have been misused will not be
guaranteed or repaired. Printed specifications are only indicative. The manufacturer does not accept any responsibility for range reductions or
malfunctions caused by environmental interference. The manufacturer's responsibility for damage caused to persons resulting from accidents of
any nature caused by our defective products, are only those responsibilities that come under Italian law.
6-1622381
rev.2
04/02/2016
Probable cause
Condominium active + automatic reclosure
deactivated
Intervention of thermical protection of the
control unit. Too high stream absorption. The
value must not be higher than 7A for more
than 3 sec.
Close
Stop
Photocell
off
on
on
Loss of electrical power.
Burned fuse
Motor cables inverted
•
The dipswitch are not correctly putted
•
The type of decoding set in the control
panel does not correspond to the type
of remote control used.
The gate is not closed
A normally closed input is not active
RUNNING AMP.SENS. Trimmer threshold
too low
Encoder broken or bad connected
ITA
ENG
Enable the automatic re-closure by turning the
trimmer in anti clockwise sense or deactivate the
condominium function (dip 4 off).
Each command is ignored for 20 seconds. Check
the motor status and their absorption.
LED STATUS
Rib/clock
on / off
possible cause
FRA
ESP
DEU
POR
Solution
Closing loop
Limit switch opening
off
on
Solution
Check the presence of electrical power and all
the connections of the electrical network.
Replace the fuse with one with the same
characteristics
Check motor wiring, inverting them if necessary
•
Put dip 1 and 2 on OFF
•
Check which decoding was set and select the
one which corresponds to the remote controls
in use.
Close (in manual) the gate. Try again to enter
into setting mode.
Check the photocells input, stop and the limit
switches. If not used, jumper it to the common
Increase the intervention value of the ampere
sensor.
Check the connections of the encoder
Pag 8 di 8