Burkert 1062 Інструкція з експлуатації - Сторінка 2

Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Позиціонери клапанів Burkert 1062. Burkert 1062 8 сторінок.

Operating Instructions
Follow this manual and proceed in accordance with
the application conditions and specification data of
the device, as referred to in the data sheets. The
position indicator shall be integrated into the process
according to the general technical guidelines. Take
appropriate actions in order to avoid unintended
operation or mutual interference in the process.
Strict observance of these conditions by the user
ensures a reliable operation and a long service life.
Specific Use
The position indicator 1062 is designed for use to
electrical position feedback and optical position
indication. It can be fitted with the Bürkert valves
2000, 2001, 2002, 2030 and 2031.
Safety Rules
Safety rules must be observed. The position
indicator should be connected by trained staff only.
Caution: Disconnect voltage before opening any
position indicator! Do not switch the valve as long as
open - danger of injury !
Operating Data
LED
green:
Valve open
red:
Valve closed
Yellow: Voltage indicator
Ambient temp.:-20 to +60 °C
Protection class: IP 65 (DIN 40 050)
Certification: Mechanic and inductive switching
elements according to VDE, IEC, UL, CSA. Inductive
NAMUR-switch element in Ex i.
Order Nr
Mechanical limit switch (gold or silver platted)
Piston
Switch
Reference
∅ mm
Ag
12/48 V
40
NO
444181
40
NF
444182
40
NO/NF 444183
50-80
NO
007462
50-80
NF
007461
50-80
NO/NF 007463
>100
NO
007465
>100
NF
007464
>100
NO/NF 007466
Piston
Switch
Reference
∅ mm
Au
12/30 V
50-80
NO
420776
50-80
NF
420777
50-80
NO/NF 420778
>100
NO
420779
>100
NF
420780
>100
NO/NF 420781
Voltage VAC/VDC
48/110 V
110/250 V
-
444184
-
444185
-
444186
420770
005415
420771
005409
420772
005416
420773
007459
420774
007458
420775
007460
Voltage VAC/VDC
48/110V
110/250 V
-
-
-
-
-
-
-
-
-
-
-
-
-2-
POSITION FEEDBACK 1062
Limit switches types
Mechanical limit switch
(Inverter as standard)
Switch operating characteristics:
Voltage
Inductive load
En
I max.
125 V
8 A
250 V
8 A
24 V =
5 A
30 V =
2 A
50 V =
0,7 A
74 V =
0,25 A
125 V =
0,03 A
250 V =
0,02 A
Inductive limit switch
Nominal voltage
Inductive contact
Max load
Output resistance
Consumption
Inductive limit switch 2 wires.
DIN 19 234 (NAMUR) Ex i
Nominal voltage
Consumption
Inductive limit switch; Voltage 10-30 VDC
Piston
Switch
∅ mm
3 wires PNP 3 wires NPN 2 wires
50-80
NO
005434
50-80
NF
005422
50-80
NO/NF 005461
>100
NO
007468
>100
NF
007467
>100
NO/NF 007469
Limit switch Exi NAMUR ; Voltage 8 VDC
Piston
Switch
Reference Switch
∅ mm
Type
2 wires NAMUR
50-80
NO
007471
50-80
NF
007470
50-80
NO/NF
007472
>100
NO
007474
>100
NF
007473
>100
NO/NF
007475
Resistance load
I max.
8 A
8 A
5 A
5 A
1 A
0,6 A
0,4 A
0,25 A
10 to 30 VDC
3 wires
2 wires
200 mA
100 mA
4,7 k
25 mA
2 mA
8 VDC
cushioned
1 mA
uncushioned > 3 mA
Reference Switch
420782
420788
420783
420789
420784
420790
420785
420791
420786
420792
420787
420793
-------
1062