Technician Settings (Cont.)
P15 – Temperature sensor calibration offset
1. Press the [SELECT] and [+] buttons
simultaneously.
2. "P10" will appear on display.
3. Use the [+] button to adjust the offset for
calibration of measured temperature.
Range: -9...+9°F / -6...+6°C
Default: 0°F / 0°C
Note: If the technician did not manually exit
testcomissioning mode, the unit will automatically
return to normal mode after 5 hours.
Save changes and Return to Normal Display
In order to save changes and return to normal
display, move DIP switch S1 back to OFF
position.
IMPORTANT: Changes made to technician
parameters will not take effect as long as
DIP switch S1 is in ON position.
Restore Default Values
Important: Make sure the unit is turned OFF
(the word "OFF" should appear on display).
1. Move DIP switch S1 to ON position.
2. Press and hold the [ON] button for 10
seconds. The thermostat will beep.
3. Move DIP switch S1 back to OFF position.
Offset
Save changes and exit
technician settings mode
18
DIP switch S2 - Short measuring times
(test only)
Use DIP switch S2 to short the measuring
times as follows:
• "ON" - Short measuring times – for test/
commissioning only (measuring times will
be divided to 60).
• "OFF" - Normal operation.
Short measuring times:
A real 1 hour will take 1 minute and a real
1 minute will take 1 second.
DIP switches S3 and S4
– Not in use – must remain OFF
BMS – BACnet/Modbus
(FPC-02-OD-AB only!)
Use DIP switch S6 located on the side of
thermostat to select BMS (A,B) network protocol:
• S6 ON – BACnet
• S6 OFF - MODBUS
S3 OFF,
S4 OFF
Modbus
BACnet