6. Slide one end of each of the two insulated barrel connectors
over the bare portion of the conductors. Crimp the barrel con-
nectors on using a crimping tool.
7. Slide a 3" length of heat shrink tubing over and past the barrel
connectors.
8. Insert entire assembly into NEMA 4 or 4X Electrical Junction
Box. Junction box should be protected from weather if possible.
9. Strip the incoming power leads and ground wire to expose a
3/8" length of bare conductor. Insert the bared portion of the
power leads into the other end of the insulated barrel connec-
tors and crimp them.
GENERAL
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
1347 HEIL QUAKER BLVD., LAVERGNE, TN 37086
Phone: (615) 793-3900
10. Center the 3" length of heat shrink tubing over the connection.
Apply heat evenly to shrink tubing around the heating cable,
barrel connectors and power leads.
Center 3" heat shrink tube over
the connection. Apply heat.
11. While the shrink tubing is still hot, gently squeeze the shrink
tubing between the power leads with needle-nose pliers and
hold until cool. The shrink tubing must remain visibly sealed
when the pliers are removed. If the tubing does not remain
sealed, reheat the tubing and try again.
Use needle-nose pliers to gently
squeeze hot shrink tubing
power leads.
12. Insert the end of the braided pigtail into one end of the unin-
sulated (silver) barrel connector and crimp it. Insert the
stripped end of the ground wire into the other end of the barrel
connector and crimp it.
13. Carefully push the connected wires into the power termination
box and secure the cover. Screw the 1/2" compression cable
connector into the power termination box to form a water-tight
seal.